Appendix
Batch Controller RA33
64
Hauser
Reg. 9 to 11
Specify which values can be read out.
Value
500000-03 Choose the value which should be transmitted.
Analysis
500001-03 Select which counter (e.g. interval, daily counter etc.) is to
be transmitted.
Only if a counter has been selected for "Value".
Reg. 12 to 14
Specify which values can be read out.
Value
500000-04 Choose the value which should be transmitted.
Analysis
500001-04 Select which counter (e.g. interval, daily counter, etc.) is
to be transmitted.
Only if a counter has been selected for "Value".
…
…
…
Reg. 87 to 89
Specify which values can be read out.
Value
500000-29 Choose the value which should be transmitted.
Analysis
500001-29 Select which counter (e.g. interval, daily counter etc.) is to
be transmitted.
Only if a counter has been selected for "Value".
Device options
Hardware and software options.
Optional outputs
990000-00
Communication
990001-00
Protocol
990007-00
CompeRTD
990009-00
Inputs
Settings for the analog and digital inputs.
Flow
Settings for the flow input.
Signal type
210000-00 Select the signal type connected.
4 to 20 mA (DP Flow):
Input for flow measurements based on the differential
pressure method (e.g. orifice plate)
Pulse U+IB+IC:
Input for active voltage pulses and contact sensors as per
EN 1434-2, Class IB + IC:
Pulse Cl. ID+IE:
Pulse input for contact sensors as per EN 1434-2, Class ID
+ IE:
Pulse (current):
Current pulse input:
≤
8 mA Low level,
≥
13 mA High
level.
Channel ident.
210001-00 Name of the measuring point connected to this input.
Customized text, 6 characters.
Pulse input
210002-00 Define whether the pulse input is a fast (up to 12.5 kHz)
or slow (up to 25Hz) pulse input.
Only if Pulse has been selected as the signal type.
Pulse Value
210003-00 Pulse factor = factor which, multiplied by an input
impulse, yields the physical value. Example: 1 pulse corre-
sponds to 5 m
3
-> enter "5" here. Decimal number, max.
8 digits including decimal separator.
Only if Pulse has been selected as the signal type.
Unit
210004-00 Specify the technical (physical) unit for the measuring
point connected to this input.