Wiring
Batch Controller RA33
18
Hauser
!
Note!
To ensure the highest level of accuracy, we recommend using the RTD 4-wire connection, as this
compensates for measurement inaccuracies caused by the mounting location of the sensors or the
line length of the connecting cables.
Density
4.4
Outputs
4.4.1
Analog output
This output can be used either as a 0/4 to 20 mA current output or as a voltage pulse output. The
output is galvanically isolated. For the terminal assignment, refer to
15.
4.4.2
Pulse output
Active voltage pulses are output at the pulse output.
Voltage level:
• 0 to 2 V corresponds to Low level
• 15 to 20 V corresponds to High level
Maximum output current: 22 mA
4.4.3
Open collector output
The two digital outputs can be used as status or pulse outputs. Make the selection in the following
menus: Setup
É
Advanced setup or Expert
É
Outputs
É
Open Collector
Temperature transmitter con-
nection
a0014186
1 = without external power supply of the transmitter, 2 = with external power supply of
the transmitter
Terminals 52, 53: T warm
Terminals 54, 55: T cold
Density sensor connection
1 = without external power supply of the pressure sensor, 2 = with external power sup-
ply of the pressure sensor