Proline Promass O 100 HART
System integration
Hauser
45
9.3
Other settings
9.3.1
Burst mode functionality in accordance with HART 7
Specification
Navigation
"Expert" menu → Communication → HART output → Burst configuration → Burst
configuration 1 to 3
Structure of the submenu
Burst configuration 1 to 3
→
Burst mode
Burst command
Burst variable 0
…
Burst variable 7
Burst trigger mode
Burst trigger level
Burst min period
Burst max period
Parameter overview with brief description
Parameter
Description
Selection / User entry
Factory setting
Burst mode #
Activation of the HART burst mode for burst
message X.
An external pressure or temperature
sensor must also be in the Burst mode.
• Off
• On
Off
Burst command #
Select the HART command that is sent to the
HART master.
•
Command 1
option:
Read out the primary variable.
•
Command 2
option:
Read out the current and the main
measured value as a percentage.
•
Command 3
option:
Read out the dynamic HART variables and
the current.
•
Command 9
option:
Read out the dynamic HART variables
including the related status.
•
Command 33
option:
Read out the dynamic HART variables
including the related unit.
•
Command 48
option:
Read out the complete device diagnostics.
• Command 1
• Command 2
• Command 3
• Command 9
• Command 33
• Command 48
Command 2