Diagnostics and troubleshooting
Proline Promag L 400 HART
112
Hauser
311
Electronic failure
1. Reset device.
2. Contact service.
F
Alarm
311
Electronic failure
Maintenance required!
1. Do not perform reset.
2. Contact service.
M
Warning
382
Data storage
1. Insert DAT module.
2. Replace DAT module.
F
Alarm
383
Memory content
1. Restart device.
2. Check or replace DAT module.
3. Contact service.
F
Alarm
*
Diagnostic behavior can be changed: "Adapting the diagnostic behavior" section (
Diagnostic
number
Short text
Remedy information
Status
signal
from the
factory
Diagnostic behavior
from the factory
Diagnostics for the configuration
201
Device malfunction
1. Restart device.
2. Contact service.
F
Alarm
410
Data transfer
1. Check connection.
2. Retry data transfer.
F
Alarm
411
Up-/download active
Up-/download active, please wait
C
Warning
431
Trim
Carry out trim.
C
Warning
437
Incompatible
configuration
1. Restart device.
2. Contact service.
F
Alarm
438
Dataset
1. Check data set file.
2. Check device configuration.
3. Up- and download new
configuration.
M
Warning
441
Current output 1
1. Check process.
2. Check current output settings.
S
Warning
*
442
Frequency output 1-2
1. Check process.
2. Check frequency output setting.
S
Warning
*
443
Pulse output 1-2
1. Check process.
2. Check pulse output setting.
S
Warning
*
453
Flow override
Deactivate flow override.
C
Warning
484
Simulation failsafe mode Deactivate simulation.
C
Alarm
485
Simulation process
variable
Deactivate simulation.
C
Warning
491
Simulation current
output 1
Deactivate simulation.
C
Warning
492
Simulation frequency
output 1-2
Switch off frequency output simulation. C
Warning
493
Simulation pulse output
1-2
Switch off pulse output simulation.
C
Warning