Proline Cubemass C 100 HART
Technical data
Hauser
103
Pulse value
Adjustable
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
Frequency output
Output frequency
Adjustable: 0 to 12
500 Hz
Damping
Adjustable: 0 to 999 s
Pulse/pause ratio
1:1
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
The range of options increases if the measuring device has one or more
application packages.
Switch output
Switching behavior
Binary, conductive or non-conductive
Switching delay
Adjustable: 0 to 100 s
Number of switching
cycles
Unlimited
Assignable functions
• Off
• On
• Diagnostic behavior
• Limit value
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Totalizer 1-3
• Flow direction monitoring
• Status
• Partially filled pipe detection
• Low flow cut off
The range of options increases if the measuring device has one or more
application packages.
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output 4 to 20 mA
4 to 20 mA
Failure mode
Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value