Proline Cubemass C 100 HART
Commissioning
Hauser
59
10.2.5 Configuring the pulse/frequency/switch output
The
Pulse/frequency/switch output 1
submenu contains all the parameters that must be
configured for the configuration of the selected output type.
Pulse output
Navigation
"Setup" menu → Pulse/frequency/switch output
Structure of the submenu for the pulse output
Pulse/frequency/switch output
→
Operating mode
Assign pulse output
Value per pulse
Pulse width
Failure mode
Invert output signal
Parameter overview with brief description
Parameter
Description
Selection / User entry
Factory setting
Operating mode
Define the output as a pulse, frequency or
switch output.
• Pulse
• Frequency
• Switch
Pulse
Assign pulse output
Select process variable for pulse output.
• Off
• Mass flow
• Volume flow
• Corrected volume flow
• Target mass flow
• Carrier mass flow
Off
Mass unit
Select mass unit.
Result
The selected unit is taken from:
Mass flow
unit
parameter
Unit choose list
Country-specific:
• kg
• lb
Volume unit
Select volume unit.
Result
The selected unit is taken from:
Volume
flow unit
parameter
Unit choose list
Country-specific:
• l
• gal (us)
Value per pulse
Enter measured value at which a pulse is
output.
Signed floating-point number
0
Pulse width
Define time width of the output pulse.
0.05 to 2
000 ms
100 ms
Failure mode
Define output behavior in alarm condition.
• Actual value
• No pulses
No pulses
Invert output signal
Invert the output signal.
• No
• Yes
No