Proline Cubemass C 100 HART
Installation
Hauser
19
DN
Ø orifice plate, pipe restriction
[mm]
[in]
[mm]
[in]
1
¹⁄₂₄
0.8
0.03
2
¹⁄₁₂
1.5
0.06
4
¹⁄₈
3.0
0.12
6
¹⁄₄
5.0
0.20
Orientation
The direction of the arrow on the sensor nameplate helps you to install the sensor
according to the flow direction (direction of medium flow through the piping).
Orientation
Recommendation
A
Vertical orientation
A0015591
B
Horizontal orientation, transmitter at
top
A0015589
C
Horizontal orientation, transmitter at
bottom
A0015590
D
Horizontal orientation, transmitter at
side
A0015592
1)
Applications with low process temperatures may decrease the ambient temperature. To maintain the
minimum ambient temperature for the transmitter, this orientation is recommended.
2)
Applications with high process temperatures may increase the ambient temperature. To maintain the
maximum ambient temperature for the transmitter, this orientation is recommended.
Inlet and outlet runs
No special precautions need to be taken for fittings which create turbulence, such as
valves, elbows or T-pieces, as long as no cavitation occurs → 20.
A0029322
A0029323
Installation dimensions
For the dimensions and installation lengths of the device, see the "Technical
Information" document, "Mechanical construction" section.