Commissioning
Liquisys M CCM223/253
52
Hauser
SCS monitoring functions at a glance
Functional
description
Setting
possibility
Alarm event
Application
Alarm threshold
monitoring
(P111 to P114)
(P111 to P114)
– freely
adjustable
lower alarm
threshold (AT)
– freely
adjustable
upper alarm
threshold (AT)
off
—
Applications
with
or
without
chemical
entrainment
control
only lower AT
lower AT reached or
dropped below
only upper AT
upper AT reached or
exceeded
lower and
upper AT
lower AT reached or
dropped below or upper
AT reached or exceeded
Controller
monitoring (CC:
Controller
Check,
P115 to P118
P125 to P128)
– Switch-on
period
monitoring
– Switch-off
period
monitoring
off
—
Applications
with
chemical
entrainment
control
on
Set maximum period for
permanent switch-on or
switch-off exceeded
Sensor activity
monitoring (AC:
Alternation
Check,
P115 to P118
P125 to P128)
Monitoring for
signal change
off
—
Applications
with
or
without
chemical
entrainment
control
on
Change within 1 hour
less than ±0.1 mg/l or
±1 %SAT or ±2 hPa
• ±0.01 mg/l
(CCS140/240,
Sensor 963)
• ±0.005 mg/l
(CCS141/241)
• pH ±0.01
• ±1 mV
Summary of Contents for Liquisys M CCM223
Page 109: ...Liquisys M CCM223 253 Technical data Endress Hauser 109...
Page 116: ...Appendix Liquisys M CCM223 253 116 Endress Hauser a0002639 en...
Page 120: ...Appendix Liquisys M CCM223 253 120 Endress Hauser...
Page 123: ...Liquisys M CCM223 253 Endress Hauser 123...
Page 124: ...www addresses endress com 71212626...