Operation
Liquistation CSF39
56
Hauser
10.2 General settings
10.2.1 Basic settings
Some settings are visible with optional hardware only.
Menu/Setup/General settings
Function
Options
Info
Device tag
Customized text, 32
characters
‣
Select any name for your controller, e.g. use
the TAG name.
Temperature unit
Selection
• °C
• °F
• K
Factory setting
°C
Current output range
Selection
• 0..20 mA
• 4..20 mA
Factory setting
4..20 mA
In accordance with Namur NE43, the linear
range is from 3.8 to 20.5 mA (
4..20 mA
) or
from 0 to 20.5 mA (
0..20 mA
). If the range is
exceeded or undershot, the current value stops
at the range limit and a diagnostic message (460
or 461) is output.
For HART communication, you must select
4..20
mA
.
Failure current
0.0 to 23.0 mA
Factory setting
22.5 mA
The function meets NAMUR NE43.
‣
Set the current value that should be output
at the current outputs in the event of an
error.
The value for
Failure current
should be outside the measuring range. If you decided that your
Current
output range
=
0..20 mA
you should set an error current between 20.1 and 23 mA. If the
Current
output range
=
4..20 mA
you could also define a value < 4 mA as the error current.
The device allows an error current within the measuring range. In such instances pay attention to any
effects this may have on your process.
Alarm delay
0 to 9999 s
Factory setting
0 s
The software displays only the errors that are
present longer than the set delay time. This
makes it possible to suppress messages that only
occur briefly and are caused by normal process-
specific fluctuations.
Device hold
Selection
• Disabled
• Enabled
Factory setting
Disabled
You can enable an immediate, general hold (for
sensors) here. The function acts in the same way
as the
HOLD
soft key in the screens.
10.2.2 Date and time
Menu/Setup/General settings/Date/Time
Function
Options
Info
Set date
Depends on the format
Editing mode:
Day (two-digit): 01 to 31
Month (two-digit): 01 to 12
Year (four-digit): 1970 to 2106
Set time
Depends on the format
Editing mode:
hh (hour): 00 to 23 / 0 am to 12 pm
mm (minutes): 00 to 59
ss (seconds): 00 to 59