Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Diagnostics and troubleshooting
Hauser
101
9.5.2
Check (C)
747
Alarm
F>Sensor software not
compatible to
electronics
17
0
– Sensor does not suit the
device (electronic sensor
nameplate).
– Replace sensor with a suitable
sensor.
18
748
Alarm
F>Memory failure in
signal processor
20
7
– Electromagnetic effects are
greater than specifications in
the technical data.
(
– Block off electromagnetic
effects or eliminate source of
disturbance.
17
– Main electronics defect.
– Replace main electronics.
Diagnostic
Code
Error
response
Message/description XD_
ERROR
Value Bit
BLOCK_
ERROR
Value Bit
Cause
Measure
Prio-
rity
Diagnostic
Code
Error
response
Message/description XD_
ERROR
Value Bit
BLOCK_
ERROR
Value Bit
Cause
Measure
Prio-
rity
106 Warning
C>Downloading
-
please wait
17
0
– Downloading.
– Wait for download to
complete.
61
602 Warning
C>Linearization
curve
not monoton
19
0
– The linearization table is not
monotonic increasing.
– Add to or correct linearization
table. Then accept
linearization table again.
67
604
Warning
C>Linearization table
invalid. Min. 2 points.
19
0
Note! There is no min. span for the y-points as of software version
"03.00.00".
– The linearization table has
fewer than 2 points.
1. Add to linearization table.
Perform the linearization again
if necessary.
2. Correct the linearization table
and accept it again.
68
613
Warning
C>Simulation active
17
0
– Simulation is switched on, i.e.
the device is not measuring at
present.
– Switch off simulation.
70
701 Warning
C>Adjustment
outside
sensor nominal range
17
0
– The adjustment carried out
would cause a breach of the
nominal sensor range.
– Carry out calibration again.
63
704
Alarm
C>Measurement error 20
7
– Fault in the main electronics. – Briefly disconnect device from
the power supply.
13
– Main electronics defect.
– Replace main electronics.
707 Alarm
C>X-VAL.
(TAB_XY_VALUE) of
lin. table out of edit
limits.
18
0
– At least one X-VALUE
(TAB_XY_VALUE) in the
linearization table is either
below the value for
SCALE_IN, EU_0/HYDR.
PRESS MIN. or LINEAR_
LEVEL_MIN/MIN. LEVEL or
above the value for
SCALE_IN, EU_100/HYDR.
PRESS. MAX. or
LINEAR_LEVEL_MAX/
LEVEL MAX.
– Perform calibration again
(
See Operating Instructions
BA00303P, parameter
description), Section 5).
45