Operation
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
60
Hauser
6.9.2
Performing reset via the FieldCare operating program
If operating via FieldCare, enter the code via the ENTER RESET CODE parameter (menu path:
OPERATING MENU
OPERATION).
The following table illustrates which parameters are reset by the particular reset codes.
Reset code
Description and effect
1)
7864
Total reset
– This reset resets the following parameters:
– POSITION ADJUSTMENT function group
– BASIC SETUP function group
– EXTENDED SETUP function group
– LINEARIZATION function group (an existing linearization table is deleted)
– TOTALIZER SETUP function group
– OUTPUT group
– INFO function group, TAG_DESC parameter
– MESSAGES function group
– All configurable messages ("Error" type) are set to "Warning".
93, Section 9.2 "Diagnostic information on local display" and
Section 9.6 "Response of outputs to errors".
– USER LIMITS function group
– Any simulation which may be running is ended.
– The device is restarted.
333
User reset
– This reset resets the following parameters:
– POSITION ADJUSTMENT function group
– BASIC SETUP function group, apart from customer-specific units
– EXTENDED SETUP function group
– TOTALIZER SETUP function group
– OUTPUT group
– Any simulation which may be running is ended.
– The device is restarted.
2710
Reset Level measuring mode
– Depending on the settings for the LEVEL MODE, LIN MEASURAND, LINd
MEASURAND or COMB. MEASURAND parameters, the parameters needed for
this measuring task will be reset.
– Any simulation which may be running is ended.
– The device is restarted.
Example LEVEL MODE = linear and LIN. MEASURAND = level
• HEIGHT UNIT = m
• CALIBRATION MODE = wet
• EMPTY CALIB. = 0
• FULL CALIB. = sensor end value converted to mH
2
O, e.g. for a 500 mbar (7.5 psi)
sensor : 50.99 mH
2
O
2509
Sensor adaption reset
– This reset resets the upper and lower sensor calibration limit and the value for
position adjustment.
– POSITION ADJUSTMENT function group
– PRESSURE_1_LOWER_CAL/LO_TRIM_MEASURED and
PRESSURE_1_HIGHER_TRIM_MEASURED/HI_TRIM_MEASURED parameters
These parameters are not available by means of the FieldCare operating
program.
– Any simulation which may be running is ended.
– The device is restarted.
1846
Display reset
– This reset resets all parameters which have to do with how the display appears
(DISPLAY group).
– Any simulation which may be running is ended.
– The device is restarted.
8888
HistoROM reset
The measured value and event buffers are deleted. During the reset, the HistoROM
has to be attached to the electronic insert.