Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Operation
Hauser
59
6.8
Simulation
The function of the Analog Input Block, such as input and output scaling, can be simulated
as follows:
1. Set the "Simulation" DIP switch on the electronic insert to "On".
2. In the Analog Input Block, select the "Active" option by means of the SIMULATION
parameter, ENABLE_DISABLE element.
3. Set the Analog Input Block to the AUTO block mode.
4. Enter the value and status for the SIMULATION_VALUE and SIMULATION_STATUS
elements. During the simulation, the output value and status of the Pressure
Transducer Block are replaced by the simulated value and status. The OUT parameter
shows the result.
5. End simulation (SIMULATION parameter, ENABLE_DISABLE element, "Disabled"
option).
You can check your adjustment for the transmitter by means of the SIMULATION_MODE
and SIMULATION_VALUE parameters in the Diagnostic Transducer Block.
See Operating
Instructions BA303 "Description of Device Functions Cerabar S/Deltabar S/Deltapilot S",
SIMULATION_MODE and SIMULATION_VALUE parameter descriptions.
6.9
Factory setting (reset)
• Total reset: Press zero-key for at least 12 seconds. The LED on the electronic insert lights
up briefly if a reset is being carried out.
• By entering a certain code, you can completely, or partially, reset the entries for the
parameters to the factory settings. (
For the factory settings, see Operating Instructions
BA00303P "Cerabar S/Deltabar S/Deltapilot S, Description of Device Functions").
Enter the code by means of the ENTER RESET CODE parameter (OPERATION menu).
There are various reset codes for the device. The following table illustrates which
parameters are reset by the particular reset codes. Operation has to be unlocked to be able
to perform a reset (
• Any customer-specific configuration carried out by the factory is not affected by a reset
(customer-specific configuration remains). If, after a reset, you wish the parameters to be
reset to the factory settings, please contact Hauser Service.
• The OUT Value parameter may have to be rescaled after resetting with code 7864. See also
79, Section 7.9 "Scaling the OUT parameter".
6.9.1
Performing reset via an FF configuration program
If operating via an FF configuration program, enter the code by means of the
RESET_INPUT_VALUE/ENTER RESET CODE parameter in the Diagnostic Transducer Block.
The index tables on
45 ff. indicate which parameters are reset by the particular reset
code.
• The RESET FF parameter gives you the option of deleting links between function blocks
and resetting FF parameters to default values and manufacturer-specific parameters to
the factory setting.
See also Operating Instructions BA00303P, RESTART parameter
description.