Troubleshooting, Diagnoses and Maintenance
37
Table 10 Trip condition, their possible causes and remedial action
Trip condition
Possible Cause
Remedy
Motor PTC
Motor thermistor (PTC) exceeds maximum
level.
-
Check on mechanical overload on the
motor (bearings, gearbox, belt, etc.)
-
Check the motor cooling system.
-
Self-cooled motor at low speed, too high
load.
Over temp
Heat sink temperature too high:
-
Too high ambient temperature of the
VSD
-
Insufficient cooling
-
Too high current
-
Blocked or stuffed fans
-
Check the functionality of the built-in fans.
The fans
must switch on automatically if the heat sink
temperature gets too high. At power up the fans are
briefly switched on.
-
Clean fans
-
Check the cooling of the cabinet (if applicable).
Over curr F
Motor current exceeds the peak VSD current:
-
Too short acceleration time.
-
Too high motor load
-
Excessive load change
-
Soft short-circuit between phases or
phase to earth
-
Poor or loose motor cable connections
-
Check the acceleration time settings and
make them longer if necessary.
-
Check the motor load.
-
Check on bad motor cable connections
-
Check on bad earth cable connection
-
Check on water or moisture in the motor housing and
cable connections.
Over volt (Mains)
Too high DC Link voltage, due to too high
mains voltage
-
Check the main supply voltage
-
Try to take away the interference cause or
use other
main supply lines.
O(ver) volt M(ains) cut
Under voltage
Too low DC Link voltage:
-
Too low or no supply voltage
-
Mains voltage dips due to starting other
major power consuming machines on
the same line.
-
Make sure all three phases are properly connected
and that the terminal screws are tightened.
-
Check that the mains supply voltage is within the limits
of the VSD.
-
Try to use other mains supply lines if dip is caused by
other machinery
Trip
(rotation monitor)
The exchanger rotor does not rotate
The rotor rotates
-
Check drive belt
-
check that indication is given when the magnet passes
the sensor see chapter 6.2.1 page 21. If no indication,
replace the rotation sensor.
-
Check function of the rotatio
n sensor: Measure with a
Multimeter between terminal 11 and 16, correct sen-
sor measures < 1V when the magnet passes the sen-
sor.-
Desat
Overload condition in the DC-link:
-
Hard short-circuit between phases or
phase
to earth
-
Saturation of current measurement
circuiting
-
Earth fault
-
Desaturation of IGBTs
-
Peak voltage on DC link
-
Check on bad motor cable connections
-
Check on bad earth cable connection
-
Check on water or moisture in the motor housing and
cable connections
-
See overvoltage trips
Power Fault
Error on power board.
-
Check mains supply voltage
Fan Error
Error in fan module
-
Check for clogged air inlet filters in panel door and
blocking material in fan module.
Summary of Contents for EMX-D
Page 1: ......
Page 2: ...Emotron EMX D Drive system for rotary heat exchanger Instruction manual English...
Page 3: ......
Page 7: ......
Page 9: ...Emotron AB 01 5016 01r0...
Page 11: ...4 Emotron AB 01 5016 01r0...
Page 19: ...12 Installation Emotron AB 01 5016 01r0...
Page 25: ...18 Control Connections Emotron AB 01 5016 01r0...
Page 33: ...26 Operation via the Control Panel Emotron AB 01 01 5016 01r0...
Page 41: ...34 Functional Description Emotron AB 01 5016 01r0...
Page 49: ...42 Technical Data Emotron AB 01 5016 01r0...