28
Functional Description
Emotron AB 01-5016-01r0
Mot Prio ref [O14]
Here you can set desired speed on outgoing shaft, to shift to
when terminal 17 and 11 is shorted
.
Purge time [O15]
This function is used to set desired purge time. This means
that the rotor will rotate during set time (Purge time) every
10 minutes.
Purge speed [O16]
Here you can set desired speed of outgoing shaft during
purge.
Hold torque [O17]
When the control signal is low and you do not want heat
recovery, it can happen that the fans makes the heat
exchanger wheel rotate. To avoid this you can apply a hold
torque keeping the rotor standing still with electronic brak-
ing.
MCC [O18]
Special menu for humidity rotors (if installed), not used for
normal application. In this mode there is special transfer
function. (Fig. 3, page 7).
By setting MCC to “On” following values will be changed:
MCC time [O19]
Time for stand still. Default value should normally not be
changed. Default value (0.0s) means continuous MCC
mode.
MCC speed [O1A]
In this menu you can adjust the MCC speed.
Default:
200.00 rpm
Range
0-200rpm
Resolution
0.01 rpm
Default:
12 s
Range
0 - 30s
Resolution
0.001s
Default:
10 rpm
Range
0 - 200 rpm
Resolution
0.01 rpm
Default:
Off
Off
No hold torque
On
Hold torque on
O14 Mot Prio ref
Stp
200rpm
A
O15 Purge time
Stp
12s
A
O16 Purge speed
Stp
10rpm
A
O17 Hold torque
Stp
off
A
Default:
Off
Off
0
Normal operation
On
1
Change menu 012, 13, 14,15 and 16
Menu
Setting
Gearbox ratio [O12]
15.5
Maximum motor speed [O13]
135 rpm
Mot Prio ref [O14]
135 rpm
Purge time [O15]
12 s
Purge speed [O16]
6,75 rpm
Default:
0.0 s
Range
0.0 - 30s
Resolution
0.001 s
Default:
6.5 rpm
Range
0 - 200 rpm
Resolution
0.01 rpm
O18 MCC
Stp
Off
A
O19 MCC
time
Stp
0.0 s
A
O1A MCC
speed
Stp
6.5 rpm
A
Summary of Contents for EMX-D
Page 1: ......
Page 2: ...Emotron EMX D Drive system for rotary heat exchanger Instruction manual English...
Page 3: ......
Page 7: ......
Page 9: ...Emotron AB 01 5016 01r0...
Page 11: ...4 Emotron AB 01 5016 01r0...
Page 19: ...12 Installation Emotron AB 01 5016 01r0...
Page 25: ...18 Control Connections Emotron AB 01 5016 01r0...
Page 33: ...26 Operation via the Control Panel Emotron AB 01 01 5016 01r0...
Page 41: ...34 Functional Description Emotron AB 01 5016 01r0...
Page 49: ...42 Technical Data Emotron AB 01 5016 01r0...