Emotron AB 01-5016-01r0
Getting Started
19
5.
Getting Started
This chapter is a step by step guide showing you the quickest
way to get the motor shaft turning.
First there is general information of how to connect mains,
motor and control cables. The next section describes how to
use the function keys on the control panel. The subsequent
examples how to program/set and run the VSD and motor.
5.1
Connect the mains and
motor cables
Dimension the mains and motor cables according to local
regulations. The cable must be able to carry the VSD load
current.
Connect mains cables and motor cables according to chapter
§ 3.4.1Mains cables, page 10, § 3.4.2Motor cables, page 10.
5.2
Remote control
In this example external signals are used to control the VSD/
motor.
5.2.1 Connect control cables and set
direction of rotation
Here you will make up the minimum wiring for starting.
In this example (Fig. 14) the motor/VSD will run with right
rotation (clockwise).
To comply with the EMC standard, use screened control
cables with plaited flexible wire up to 1.5 mm
2
or solid wire
up to 2.5 mm
2
.
1. Connect a reference value between terminals 7 (Com-
mon) and 2 (AnIn 1) as in Fig. 14.
From factory there is a jumper between terminal 11(+24
VDC) and 9 (DigIn2, RUNR) to set the motor to run right
(clockwise).
2. For remote control, remove the jumper and connect an
external start button between terminal 11 and 9 as in
Fig. 14. If you would like the motor to run left, use ter-
minal 11 and 8 instead.
Fig. 14 Wiring
5.2.2 Switch on the mains
Mount the front cover on the VSD. Once the mains is
switched on, the internal fan in the VSD will run for 5 sec-
onds.
5.2.3 Run the drive system
Now the installation is finished, and you can press the exter-
nal start button to start the motor.
When the motor is running the main connections are OK.
X2
X3
X1
1
12
22
11
41
42
43
31
32
33
51
52
2
3
4
5
6
7
8
9
10
13
14
15
16
17
18
19
20
21
Start forward
Reference
0 - 10 V
+
0V
(Run Right)
Summary of Contents for EMX-D
Page 1: ......
Page 2: ...Emotron EMX D Drive system for rotary heat exchanger Instruction manual English...
Page 3: ......
Page 7: ......
Page 9: ...Emotron AB 01 5016 01r0...
Page 11: ...4 Emotron AB 01 5016 01r0...
Page 19: ...12 Installation Emotron AB 01 5016 01r0...
Page 25: ...18 Control Connections Emotron AB 01 5016 01r0...
Page 33: ...26 Operation via the Control Panel Emotron AB 01 01 5016 01r0...
Page 41: ...34 Functional Description Emotron AB 01 5016 01r0...
Page 49: ...42 Technical Data Emotron AB 01 5016 01r0...