32
Functional Description
Emotron AB 01-5016-01r0
7.5.3
Stored values [730]
The shown values are the actual values built up over time.
Values are stored at power down and updated again at power
up.
Run Time [731]
Displays the total time that the VSD has been in Run Mode.
Displays the total time that the VSD has been connected to
the mains supply. This timer cannot be reset.
Displays the total energy consumption.
7.6
View Trip Log [800]
Main menu with parameters for viewing all the logged trip
data. In total the VSD saves the last 9trips in the trip mem-
ory. The trip memory refreshes on the FIFO principle (First
In, First Out). Every trip in the memory is logged on the
time of the Run Time [731] counter. At every trip, the
actual values of several parameters are stored and available
for troubleshooting.
7.6.1
Trip Message log [810]
Display the cause of the trip and what time it occurred.
When a trip occurs the status menus are copied to the trip
message log. There are nine trip message logs [810]–[890].
When the tenth trip occurs the oldest trip will disappear..
The information from the status menus are copied to the
trip message log when a trip occurs.
Unit:
h: m: s (hours: minutes: seconds)
Range:
0h: 0m: 0s–65535h: 59m: 59s
Unit:
h: m: s (hours: minutes: seconds)
Range:
0h: 0m: 0s–65535h: 59m: 59s
NOTE: At 65535 h: 59 m the counter stops. It will not
revert to 0h: 0m.
Unit:
kWh
Range:
0.0–999999kWh
Stp
h:m:s
Stp
h:m:s
Stp
kWh
Unit:
h: m (hours: minutes)
Range:
0h: 0m–65355h: 59m
Trip menu
Copied from
Description
Process Value
Motor speed
Torque
Shaft Power
Electrical Power
Current
Output voltage
Frequency
DC Link voltage
81A
71A
Heat sink temperature
VSD Status
Digital input status
Digital output status
Analogue input status 1-2
Analogue input status 3-4
Analogue output status 1-2
Run Time
Mains Time
Energy
81O
310
View reference
8x0 Trip message
Stp
h:mm:ss
Stp
132:12:14
Summary of Contents for EMX-D
Page 1: ......
Page 2: ...Emotron EMX D Drive system for rotary heat exchanger Instruction manual English...
Page 3: ......
Page 7: ......
Page 9: ...Emotron AB 01 5016 01r0...
Page 11: ...4 Emotron AB 01 5016 01r0...
Page 19: ...12 Installation Emotron AB 01 5016 01r0...
Page 25: ...18 Control Connections Emotron AB 01 5016 01r0...
Page 33: ...26 Operation via the Control Panel Emotron AB 01 01 5016 01r0...
Page 41: ...34 Functional Description Emotron AB 01 5016 01r0...