MODBUS Termination Blocks
Default Parameter Map • 59
LAU
n
AUX
Synchronization
n; Y
This parameter indicates if the AUX
command of the section will act also on
all the other sections:
n
= the light command acts only in the
local section.
Y
= the light command is sent to all the
other sections.
LES
n
Energy Saving
Synchronization
n; Y
This parameter indicates if the energy
saving command of the section will act
also on all the other sections:
n
= the Energy Saving command acts
only in the local section.
Y
= the Energy Saving command is sent
to all the other sections.
LSd
n
Remote probe
displaying
n; Y
This parameter indicates if the section
has to display the local probe value or
the value coming from another section:
n
= the displayed value is the local
probe value.
Y
= the displayed value is from another
section (which has parameter
LdS = Y
).
LPP
n
Pressure probe
through the LAN
n; Y
n =
the value of pressure probe is read
from the local probe.
Y =
the value of pressure probe is sent
via LAN.
LCP
n
Probe 4 through the
LAN
n; Y
StM
n
Cooling request
from the LAN
enables compressor
relay
n; Y
n =
not used.
Y =
a generic cooling request from the
LAN activates the solenoid valve
connected to compressor relay.
ACE
n
Cooling request
from the LAN
enable even if
compressor is
stopped by door
switch
n; Y
n =
not used.
Y =
a generic cooling request from the
LAN activates the solenoid valve
connected to compressor relay.
PROBE CONFIGURATION NTC (10KΩ a 25°C), PtC (806Ω a 0°C)
P1C
ntC
P1 configuration
nP; PtC; ntC; CtC; PtM
nP
= not present;
PtC
= Ptc;
ntC
= ntc;
CtC
= ntc US;
PtM
= Pt1000
Ot
0
P1 calibration
[-12.0°C to 12.0°C]
Allows possible offset of the thermostat
probe to adjust.
P2C
CtC
P2 configuration
nP; PtC; ntC; CtC; PtM
nP
= not present;
PtC
= Ptc;
ntC
= ntc;
CtC
= ntc US;
PtM
= Pt1000
oE
0
P2 calibration
[-12.0°C to 12.0°C]
Allows possible offset of the evaporator
probe to adjust.
P3C
nP
P3 configuration
nP; PtC; ntC; CtC; PtM
nP
= not present;
PtC
= Ptc;
ntC
= ntc;
CtC
= ntc US;
PtM
= Pt1000
Label
Value
Description
Range
Notes
Table 24-1
- Default Parameter Map