MODBUS Termination Blocks
Default Parameter Map • 55
dAo
0.0
Delay of
temperature alarm
at start-up
0.0 to 24h00min
After powering the device: time interval
between the detection of the
temperature alarm condition and the
alarm signaling.
Format:
hours.10min
Resolution:
10min
EdA
30
Alarm delay at the
end of defrost
0 to 255min
At the end of the defrost cycle: time
interval between the detection of the
temperature alarm condition and the
alarm signaling.
dot
15
Temperature alarm
exclusion after door
open
0 to 255min
-
Sti
nU
Stop regulation
interval
0.0 to 24h00min; nU
After regulating continuously for
Sti
time, the valve closes for
Std
time to
prevent ice from forming.
Format:
hours.10min
Resolution:
10min
Std
1
Stop duration
1 to 255min
Defines the stop regulation time after
Sti
.
During this interval, the display
shows
StP
message.
tbA
n
Silencing alarm
relay by pressing a
key
n; Y
-
OUTPUT CONFIGURATION
OA1
CPr
Relay on terminals
11-12 configuration
nU; CPr; dEF; FAn; ALr;
LiG; AUS; db; onF; AC
nU
= not used;
CPr
= compressor/
valve;
dEF
= defrost;
FAn
= Fan;
ALr
= Alarm;
LiG
= Light;
AUS
= auxiliary;
db
= heater for neutral
zone (not available with
CrE = Y
);
onF
= ON/OFF;
AC
= anti-sweat;
E3r
: solenoid valve for EX3 or for
mechanical solenoid valve
OA6
AUS
Relay on terminals
17-18 configuration
nU; CPr; dEF;
FAn; ALr; LiG;
AUS; db; onF; AC
nU
= not used;
CPr
= compressor /
valve;
dEF
= defrost;
FAn
= Fan;
ALr
= Alarm;
LiG
= Light;
AUS
= auxiliary;
db
= heater for neutral
zone (not available with
CrE = Y
);
onF
= ON/OFF;
AC
= anti-sweat;
E3r
: solenoid valve for EX3 or for
mechanical solenoid valve
OA7
nU
Relay on terminals
nU; CPr; dEF; FAn; ALr;
LiG; AUS; db; onF; AC
nU
= not used;
CPr
= compressor/
valve;
dEF
= defrost;
FAn
= Fan;
ALr
= Alarm;
LiG
= Light;
AUS
= auxiliary;
db
= heater for neutral
zone (not available with
CrE = Y
);
onF
= ON/OFF;
AC
= anti-sweat;
E3r
: solenoid valve for EX3 or for
mechanical solenoid valve
Label
Value
Description
Range
Notes
Table 24-1
- Default Parameter Map
Summary of Contents for XM678D
Page 2: ......
Page 3: ...Emerson 1065 Big Shanty Road NW Suite 100 Kennesaw GA 30144 770 425 2724 www emerson com ...
Page 4: ......
Page 8: ......
Page 74: ...Figure 1 MODBUS COM Wiring Diagram 66 XM678D I O Manual 026 1219 Rev 3 ...