46 • XM678D I&O Manual
026-1219 Rev 3
Fot
nU
Manual opening
0 to 100%
nU
Allows the valve opening to force to the
specified value. This value overwrites
the one calculated by PID algorithm.
CAUTION! It must be [
Fot = nU
] to
have correct superheat regulation.
PA4
0
Probe value at
4mA or at 0V
Meas
Unit
Range
BAR
[PrU=rE]
-1.0 to P20
[PrU=Ab]
0.0 to P20
PSI
[PrU=rE]
-14 to P20
[PrU=Ab]
0 to P20
dKP
[PrU=rE]
-10 to P20
[PrU=Ab]
0 to P20
Pressure value at 4mA for current probe
[4 to 20mA] or value at 0V for
ratiometric probes. The value is
absolute or relative according to
PrU
parameter.
P20
200
Probe value at
20mA or at 5V
Meas
Unit
Range
BAR
[PrU=rE]
PA4 to 60.0
[PrU=Ab]
PA4 to 60.0
PSI
[PrU=rE]
PA4 to 870
[PrU=Ab]
PA4 to 870
dKP
[PrU=rE]
PA4 to 600
[PrU=Ab]
PA4 to 600
Pressure value at 20mA for current
probe [4 to 20mA] or value at 5V for
ratiometric probes. The value is
absolute or relative according to
PrU
parameter.
LPL
0
Lower Pressure
Limit for superheat
regulation
PA4 to P20
EXPERT:
When the suction pressure
goes down the lower bound
LPL
,
superheat
regulation will use a fixed
pressure value. Otherwise, the normal
pressure value will be used (according
to
PrU
parameter).
MOP
100
Maximum
operating pressure
threshold and valve
closing of
dML
value
LOP to P20
If the suction pressure exceeds the
maximum operating pressure value, the
device will signal this situation
generating the
MOP
alarm (according
to
PrU
parameter).
Label
Value
Description
Range
Notes
Table 24-1
- Default Parameter Map