MODBUS Termination Blocks
Default Parameter Map • 45
Atu
n
Minimum STABLE
superheat search
No; Yes
This parameter enables the search of the
minimum stable superheat. The lowest
admitted value is LSH+2°C.
AMS
n
Self adaptive SH
regulation enabling
No; Yes
This parameter enables the self adaptive
regulation of the superheat. CrE = no
must to be set, when this function is
enabled.
SSH
9
Superheat setpoint
[1°F to 45°F]
[0.1°C to 25.5°C]
This is the value used to regulate the
superheat.
Pb
36
Proportional band
[1°F to 108°F]
[0.1°C to 60.0°C]
The valve changes its opening on the
band
[SSH
,
SSH + Pb]
. At
SSH
value
of superheat the valve will be at 0%
(without integral contribution) and at
[SSH + Pb]
value of superheat the
valve will be at
MnF
. For values bigger
than
[SSH + Pb]
the valve is
completely opened.
rS
-3
Proportional band
reset
[-12.0°C to 12.0°C]
It allows to move the regulation band,
above or below the SH setpoint.
inC
220
Integration time for
superheat
regulation
0 to 255s
-
PEO
0
Valve opening in
case of error on
probes P5 or P6
0 to 100%
If a temporary probe error occurs, valve
opening percentage is
PEo
until
PEd
time is elapsed.
OPE
85
Start opening
percentage for the
time
SFD.
It’s not
limited by the
MnF
parameter.
0 to 100%
Opening valve percentage when the
start function is active. This phase
duration is
SFd
time.
SFd
0.0
Duration of soft
start phase with
opening at
OPE
0.0 to 42min00sec (252)
Set start function duration and post-
defrost duration.
During this phase the
alarms are neglected.
Format
: min.10sec
Resolution
: 10sec
OPd
85
Valve opening
percentage during
hot gas defrost. It’s
not limited by the
MnF
parameter.
0 to 100%
Opening valve percentage during hot
gas defrost. During hot gas defrost there
is no
SH
control.
MnF
100
Maximum
percentage of
opening admitted
(during normal
functioning)
0 to 100%
During the regulation it sets the
maximum valve opening percentage.
This value is not used during the
SFd
phase (soft start) and during hot gas
defrost, where the fixed percentage of
the valve opening is set by
oPd
.
Label
Value
Description
Range
Notes
Table 24-1
- Default Parameter Map