24 Default Parameter Map
The first column numbers are simple indexes not related to the position on the device menu. The total amount
of parameters can be different depending on the applications. SUBMENUS: V1...V30 ELECTRONIC VALVE
belongs to EEV.
Label
Value
Description
Range
Notes
EEU
ELECTRONIC
VALVE
By pressing
SET
you can enter the
electronic expansion valve submenu.
FtY
290
Kind of gas
Type of gas used by plant.
Fundamental parameter for correct
functioning of all system
.
LABEL
REFRIGERANT
OPERATING
RANGE
R22
r22
-58 to 120°F/
-50 to 60°C
134
r134A
-58 to 120°F/
-50 to 60°C
290
r290 – Propane
-58 to 120°F/
-50 to 60°C
404
r404A
-94 to 120°F/
-70 to 60°C
47A
r407A
-58 to 120°F/
-50 to 60°C
47C
r407C
-58 to 120°F/
-50 to 60°C
47F
r407F
-58 to 120°F/
-50 to 60°C
410
r410A
-58 to 120°F/
-50 to 60°C
448
r448A
-69 to 120°F/
-45 to 60°C
449
r449A
-69 to 120°F/
-45 to 60°C
450
r450A
-69 to 120°F/
-45 to 60°C
507
r507
-94 to 120°F/
-70 to 60°C
513
r513A
-69 to 120°F/
-45 to 60°C
CO2
r744 - Co2
-58 to 120°F/
-50 to 60°C
Table 24-1
- Default Parameter Map