Digital Inputs
Wiring Diagram and Connections • 13
6.12.Digital Inputs
• Terminals [
30
] through [
33
] are all free of voltage.
• Use a shielded cable for distances higher than one
meter.
For each digital input, configure the parameters:
i1P
(polarity of activation),
i1F
(function of the
input), and
i1d
(delay of signaling).
The
i1P
can be set to:
cL
= active when closed; or
oP
= active when opened.
The
i1F
parameter can be set to:
EAL
= external
alarm,
Bal
= serious lock alarm,
PAL
= pressure
switch alarm,
dor
= door switch,
dEF
= external
defrost,
AUS
= auxiliary activation command,
LiG
= light activation,
OnF
= board On/OFF,
FHU
= do not use this configuration,
ES
= day/night,
or
HdY
= do not use this configuration.
The
i1d
parameter is for the delay of activation.
For the other digital inputs, same set of parameters is
present:
i2P
,
i2F
,
i2d
,
i3P
,
i3F
,
i3d
.
6.13.Analog Output
• Can be set between 4 to 20mA and 0 to 10VDC.
• Use a CABCJ15 cable for connections.
The analog output is located near the terminal [
39
] on
a two-pin connector. The analog output can be used to
control anti-sweat heaters using a chopped phased
controller, XRPW500 (500 watt) or family, XV
xx
D
or XV
xx
K.
Figure 6-9
- Digital Inputs
Figure 6-10
- Analog Output