54 • XM678D I&O Manual
026-1219 Rev 3
ASr
1
Differential for
fan/offset for
anti-sweat heater
[-45°F to 45°F]
[-25.5°C to 25.5°C]
trA = AC:
dewpoint offset.
trA = rEG:
differential for modulating
fan regulation.
PbA
10
Proportional band
for modulating
output
[1°F to 45°F]
[0.1°C to 25.5°C]
Differential for anti-sweat heaters
AMi
0
Minimum output
for modulating
output
0 to AMA
Minimum value for analog output:
(0 to
AMA
)
AMA
100
Maximum output
for modulating
output
AMi to 100
Maximum value for analog output:
(
AMi
to 100)
AMt
20
Time with fan at
maximum speed or
ON time for relay
on anti-sweat
regulation
[10 to 60s] or
[10 to 60min]
trA = AC:
Anti-sweat heaters cycle
period.
trA = rEG:
Time with fan at maximum
speed.
The fan works at maximum speed
during this time. If intended for fan,
time is based in seconds; for anti-sweat
regulation, the time is based in minutes.
ALARM
rAL
tEr
Probe for room
temperature alarm
nP; P1; P2; P3; P4; P6;
tEr
Selects the probe used to signal the
alarm temperature.
ALC
Ab
Room temperature
alarm
configuration:
relative to setpoint
or absolute
rE; Ab
rE
= High and Low alarms related to
the setpoint.
Ab
= High and Low alarms related to
the absolute temperature.
ALU
41
High room
temperature alarm
setting
[0.0°C to 32.0°C] or
[ALL to 150.0°C]
ALC = rE:
[32°F to 90°F] or
[0.0°C to 32 °C]
ALC = Ab:
[
ALL
to 302°F] or
[
ALL
to 150°C]
When this temperature is reached and
the
ALd
delay time is expired, the
HA
alarm will be enabled.
ALL
-25
Low room
temperature alarm
setting
[0.0°C to 50.0°C] or
[-55.0°C to ALU]
ALC = rE:
[32°F to 90°F] or
[0.0°C to 32.0°C]
ALC = Ab:
[-67.0°F to
ALU
] or
[-55.0°C to
ALU
]
After this temperature is reached and
the
ALd
delay time is expired, the
LA
alarm will be enabled.
AHY
2
Differential for
room temperature
alarm
[1°F to 45°F]
[0.1°C to 25.5°C]
Threshold recovery after a temperature
alarm.
ALd
60
Room temperature
alarm delay
0 to 255min
Time interval between the detection of
an alarm condition and the
corresponding alarm signaling.
Label
Value
Description
Range
Notes
Table 24-1
- Default Parameter Map
Summary of Contents for XM678D
Page 2: ......
Page 3: ...Emerson 1065 Big Shanty Road NW Suite 100 Kennesaw GA 30144 770 425 2724 www emerson com ...
Page 4: ......
Page 8: ......
Page 74: ...Figure 1 MODBUS COM Wiring Diagram 66 XM678D I O Manual 026 1219 Rev 3 ...
Page 75: ......