74
Reference Manual
00809-0100-4107, Rev BA
Section 5: Operation and Maintenance
April 2013
Recalling Factory Trim with a Field Communicator
From the
HOME
screen, enter the fast key sequence and follow the steps within the Field
Communicator to complete the Sensor Trim.
Recalling factory trim with AMS Device Manager
Right click on the device and, under the
Method
drop down menu, move cursor over
Calibrate
and select
Restore Factory Calibration
.
1.
Click
Next
after setting the control loop to manual.
2.
Select
Sensor Trim
under
Trim to recall
and click
Next
.
3.
Follow the screen prompts to recall Sensor Trim.
Recalling factory trim - Sensor Trim using Local Operator
Interface
to recall factory Sensor Trim.
Figure 5-4. Recall Factory Trim - Sensor Trim with Local Operator Interface
5.6
Trim the analog output
The Analog Output Trim commands allow you to adjust the transmitter’s current output at the 4
and 20 mA points to match the plant standards. This trim is performed after the digital to
analog conversion so only the 4-20mA analog signal will be affected.
graphically
shows the two ways the characterization curve is affected when an analog output trim is
performed.
Device Dashboard Fast Keys
3, 4, 3
EXTENDED MENU
CALIBRAT
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
FACTORY RECALL
FACTORY RECALL
BACK TO MENU
EXIT MENU
FACTORY RECALL
SENSOR RECALL
SENSOR RECALL
ANALOG RECALL
BACK TO MENU
EXIT MENU