177
Reference Manual
00809-0100-4107, Rev BA
Appendix B: Product Certifications
April 2013
E1
ATEX Flame-Proof
Certification No. KEMA 08ATEX0090X
Applicable Standards: EN60079-0:2009, IEC60079-0:2011, EN60079-1:2007,
EN60079-26:2007
Markings
II 1/2 G
Ex d IIC T6 Ga/Gb (–50 °C
Ta
65 °C)
Ex d IIC T5 Ga/Gb (–50 °C
Ta
80 °C)
IP66
1180
Ui = 32 Vdc
Special Conditions for Safe Use (X):
1. Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a
temperature of 90 °C.
2. This device contains a thin wall diaphragm. Installation, maintenance, and use shall
take into account the environmental conditions to which the diaphragm will be
subjected. The manufacturer’s instructions for maintenance shall be followed in detail to
assure safety during its expected lifetime.
3. In case of repair, Contact Emerson Process Management for information on the
dimensions of flameproof joints.
ND
ATEX Dust
Certification No. Baseefa08ATEX0182X
Applicable Standards: EN60079-0:2012, EN 60079-31:2009
Markings:
II 1 D Ex t IIIC T50 °C T
500
60 °C Da
IP66 IP68
U
i
= 42.4 Vdc
1180
Special Conditions for Safe Use (X):
If the equipment is fitted with an optional 90 V transient suppressor, it is incapable of
isolation from earth test and this must be taken into account during installation.
IECEx Certifications
I7
IECEx Intrinsic Safety
Certification No. IECExBAS08.0045X
Applicable Standards: IEC60079-0:2011, IEC60079-11:2011
Ex ia IIC T4 Ga (–60 °C
T
a
+70 °C)
Special Conditions for Safe Use (X):
The device is not capable of withstanding the 500 V insulation test required by Clause
6.3.12 of IEC60079-11. This must be taken into account when installing the apparatus.
Table B-5. Input Parameters
U
i
= 30 V
I
i
= 300 mA
P
i
= 1.3 W
C
i
= 0 μF