Recommended External Fuses
External fuses should be chosen based upon the physical manifold configuration. Please refer to table
below for the fuse sizing chart.
External Fuse Sizing Chart
Power Consumption - Power Connector Pin for Valves and Outputs
Description
Current
Number of Solenoid Valve Coils Energized Simultaneously
___ X 0.167 A (ISO - SPA Series)
=
__________Amps
___ X 0.105 A (2012 and 2035 Series)
=
__________Amps
___ X 0.056 A (2005 Series)
=
__________Amps
___ X 0.021 A (2002 Series)
=
__________Amps
+
Total load current drawn by simultaneously energized Discrete Outputs
=
__________Amps
+
Number of I/O modules installed ___ X 0.87
*
A
=
__________Amps
+
Valve Adapter =
.134 Amps
+
Communication Node Power Consumption
=
.006
*
Amps
+
Total:
__________Amps
Surge Compensation:
X
1.25
Suggested Ex24 VDC (Valves and Outputs) Fuse Value:
__________Amps
Power Consumption – Power Connector Pin for Node and Inputs
Description
Current
Communication Node Power Consumption
=
.094 Amps
+
Total load current drawn by Sensor Devices from Discrete Inputs source
=
__________Amps
+
Number of I/O modules installed ___ X 0.080 A
=
__________Amps
+
Total:
__________Amps
Surge Compensation:
X
1.25
Suggested External Pin +24 VDC (Node and Inputs) Fuse Value:
__________Amps
The Node and Inputs Aux Power pins supply power to the node electronics. These pins must
be powered at all times for communication node and Inputs to be functional.
The internal electronic fuses exist to protect against damage due to catastrophic failure of
internal components. External fuses are always recommended for protection against power
supply failure, over-current conditions, etc…