G3
Series
PROFIBUS
‐
DP
Technical
Manual
Page
45
TDG3PTTM1-2EN
02/09
Subject to change without notice
www.numatics.com/g3
One Analog Input per Connector - M12 Female Modules
Module
Part No.
Signal Type
Short Circuit
Protection
Input Points
240-212 0-10
VDC
240-214 4-20
mA
YES – Visual
4
Input Mapping
BYTE
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
X
Input No. 1
Input No. 1
Input No. 1
Input No. 1
Input No. 1
Input No. 1
Input No. 1
Input No. 1
(LSB)
X+1
Input No. 1
(MSB)
Input No. 1
Input No. 1
Input No. 1
Input No. 1
Input No. 1
Input No. 1
Input No. 1
X+2
Input No. 2
Input No. 2
Input No. 2
Input No. 2
Input No. 2
Input No. 2
Input No. 2
Input No. 2
(LSB)
X+3
Input No. 2
(MSB)
Input No. 2
Input No. 2
Input No. 2
Input No. 2
Input No. 2
Input No. 2
Input No. 2
X+4
Input No. 3
Input No. 3
Input No. 3
Input No. 3
Input No. 3
Input No. 3
Input No. 3
Input No. 3
(LSB)
X+5
Input No. 3
(MSB)
Input No. 3
Input No. 3
Input No. 3
Input No. 3
Input No. 3
Input No. 3
Input No. 3
X+6
Input No. 4
Input No. 4
Input No. 4
Input No. 4
Input No. 4
Input No. 4
Input No. 4
Input No. 4
(LSB)
X+7
Input No. 4
(MSB)
Input No. 4
Input No. 4
Input No. 4
Input No. 4
Input No. 4
Input No. 4
Input No. 4
Diagnostic Telegram
BYTE
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
X
Allocated
and
Reserved
Allocated
and
Reserved
Allocated
and
Reserved
Allocated
and
Reserved
Power Status
for Conn. D
Power Status
for Conn. C
Power Status
for Conn. B
Power Status
for Conn. A
X+1
High Alarm
for Conn. D
Low Alarm
for Conn. D
High Alarm
for Conn. C
Low Alarm
for Conn. C
High Alarm
for Conn. B
Low Alarm
for Conn. B
High Alarm
for Conn. A
Low Alarm
for Conn. A