G3
Series
PROFIBUS
‐
DP
Technical
Manual
Page
44
TDG3PTTM1-2EN
02/09
Subject to change without notice
www.numatics.com/g3
Analog I/O Modules
Analog I/O Module Rules
The analog I/O modules follow the same rules as the digital I/O modules. The maximum total number of
modules on the Sub-Bus is 16. The analog modules allow the user to control and/or read analog devices using
an analog signal. These modules are available in two analog signal types: 0-10 V and 4-20 mA, and are available
in two different I/O configurations: 2 analog input channels/ 2 analog outputs channels (2AI/2AO) or 4 analog
input channels (4AI).
4 Channel I/O - M12 Female Modules
Specifications
-
Input Resolution: 16 bit (65,536 Counts)
-
Output Resolution: 16 bit (65,536 Counts)
-
Settling Time: 3 ms Max
-
Absolute Precision:
≤
1.0% of Signal
-
Voltage Input Impedance: 0-10VDC – 40K Ohms
-
Current Input Impedance: 250 Ohms
-
Input Cutoff Frequency: 100 Hz
Module
Part No.
Signal Type
Input Points
Output Points
Short Circuit Protection
240-212
0 - 10V
4
0
240-213
0 - 10V
2
2
240-214
4 - 20mA
4
0
240-215
4 - 20mA
2
2
Yes