Parameter description
protocol
Performance
Menu
6
The
drive
event
flags
indicate
certain
actions
have
occurred
within
the
drive
as
described
below.
Pr
6.42
and
Pr
6.43
provide
a
method
of
controlling
the
sequencer
inputs
and
other
functions
directly
from
a
single
control
word.
If
Pr
6.43
=
0
the
shown
below.
Bits
0-7
and
bit
9:
sequencing
control
Parameter
structure
Keypad
and
format
Advanced
parameter
descriptions
Serial
comms
Defaults
loaded
(Bit
0)
The
drive
sets
bit
0
when
defaults
have
been
loaded
and
the
associated
parameter
save
has
been
completed.
The
drive
does
not
reset
this
flag
except
at
power-up.
This
flag
is
intended
to
be
used
by
SM-Applications
Solutions
Module
programs
to
determine
when
the
default
loading
process
is
complete.
For
example
an
application
may
require
defaults
that
are
different
from
the
standard
drive
defaults.
These
may
be
loaded
and
another
parameter
save
initiated
by
the
SM-Applications
module
when
this
flag
is
set.
The
flag
should
then
be
cleared
so
that
the
next
event
can
be
detected.
control
word
has
no
effect,
if
Pr
6.43
=
1
the
control
word
is
enabled.
Each
bit
of
the
control
word
corresponds
to
a
sequencing
bit
or
function
as
When
the
control
word
is
enabled
(Pr
6.43
=
1),
and
the
Auto/manual
bit
(bit7)
are
both
one,
bits
0
to
6
and
bit
9
of
the
control
word
become
active.
The
equivalent
parameters
are
not
modified
by
these
bits,
but
become
inactive
when
the
equivalent
bits
in
the
control
word
are
active.
When
the
bits
are
active
they
replace
the
functions
of
the
equivalent
parameters.
For
example,
if
Pr
6.43
=
1
and
bit
7
of
Pr
6.42
=
1
the
drive
enable
is
no
longer
controlled
by
Pr
6.15,
but
by
bit
0
of
the
control
word.
If
either
Pr
6.43
=
0,
or
bit
7
of
Pr
6.42
=
0,
the
drive
enable
is
controlled
by
Pr
6.15.
Bit
8:
Analog/preset
reference
When
the
control
word
is
enabled
(Pr
6.43)
bit
8
of
the
control
word
becomes
active.
(Bit
7
of
the
control
word
has
no
effect
on
this
function.)
The
state
of
bit
8
is
written
to
Pr
1.42.
With
default
drive
settings
this
selects
analog
reference
1
(bit8
=
0)
or
preset
reference
1
(bit8
=
1).
If
any
other
drive
parameters
are
routed
to
Pr
1.42
the
value
of
Pr
1.42
is
undefined.
Mentor
MP
Advanced
User
Guide
105
Issue
Number:
4
www.onxcontrol.com
Bit
Function
Equivalent
parameter
0
Drive
enable
Pr
6.15
1
Run
forward
Pr
6.30
2
Jog
Pr
6.31
3
Run
reverse
Pr
6.32
4
Forward/reverse
Pr
6.33
5
Run
Pr
6.34
6
Not
stop
Pr
6.39
7
Auto/manual
8
Analog/Preset
reference
Pr
1.42
9
Jog
reverse
Pr
6.37
10
Reserved
11
Reserved
12
Trip
drive
13
Reset
drive
Pr
10.33
14
Keypad
watchdog
6.42
Control
word
Coding
Bit
SP
FI
DE
Txt
VM
DP
ND
RA
NC
NV
PT
US
RW
BU
PS
1
1
1
Range
0
to
32,767
Default
0
Update
rate
Bits
0
–7:
4
ms
read,
Bits
8-15:
Background
read
6.41
Drive
event
flags
Coding
Bit
SP
FI
DE
Txt
VM
DP
ND
RA
NC
NV
PT
US
RW
BU
PS
1
1
1
Range
0
to
65535
Default
0
Update
rate
Background
write
6.43
Control
word
enable
Coding
Bit
SP
FI
DE
Txt
VM
DP
ND
RA
NC
NV
PT
US
RW
BU
PS
1
1
1
Default
0
Update
rate
Related
to
bits
0-7:
4
ms
read,
related
to
bits
8-15:
Background
read