6.4 --- LAN local network management:

Stand---by and Cascade modes

The control of the units in stand---by is completely automatic,

thanks to the possibility of connection with the Microface con-

trol. A unit in stand---by is automatically activated in case of

alarm locking the main unit; this occurs even if the main unit is

switched off or disappears from the system due to a failure on

the control connecting network (bus).

The hourly rotation of the stand---by units occurs automatically

every 24 hours, so as to enable an even wear of the system com-

ponents.

If the system is connected with the Hiromatic interface, it is pos-

sible to set a different rotation control.

Activating the Cascade function, if several units are simulta-

neously on with the same Set Point, the temperature used for

the control is the average of the detected ones: in cooling mode,

the proportional band is divided in as many parts as the double

of units belonging to the system, so as to shut the total available

refrigerating capacity.

The activation of the Freecooling mode (if installed) is sequen-

tial on the different units forming the system, and precedes the

possible activation of the cooling with compressor.
The Fig. d), shown as an example, represents the operation of a

system formed by three units.

Fig. d) System with 3 units in cascade --- Microface control

Set

_

C

Cooling

Heating

3

Freecooling mode

1

2

3

Compressor cooling mode

1

1

2

2

3

P Band

P Band

Set

_

C

Cooling

Heating

6.5 --- Alarm control

The two alarm contacts available on the terminal board of the

electric board are:

1) General alarm (highest priority), including:

S

compressor low pressure

S

compressor high pressure (reset on the pressure switch)

S

sensor fault

S

memory fault

S

fan fault

2) General warning (lowest priority), including:

S

high temperature

S

low temperature

A further general warning is available in the unit equipped with

heating, signalling the following abnormal condition:

heater thermostat (reset on thermostat)

Note:

S

An alarm causes the unit to stop and the unit in stand---by

(if available) to intervene.

S

A warning does not stop the unit.

S

Both the alarm and the warning activate sight and sound

signals.

S

Both the alarm and the warning must be reset manually on

the Microface.

In case the safety heater thermostat intervenes, the reset must

be carried out on the thermostat, following the same instruc-

tions as before.

6.6 --- Alarm board

(optional)

Besides the components described for the standard configura-
tion, an alarm card --- which can be supplied as optional --- there

are relay contacts which have the following alarms:
1) compressor high and low pressure
2) High temperature
3) Low temperature
4) Clogged filter alarm
5) Fan fault

These alarms control the unit in the same way as described in

the previous paragraph.

For the detailed description of the alarms, see the Microface

manual enclosed.

7 --- Calibrations

S

The air conditioner has already been factory---tested and

calibrated as described below (see Tab. 5).

S

For the MICROFACE calibrations refer to the relevant manu-
al (to avoid wrong operations do not use temperature and

rel. humidity set points/proportional bands which differ ex-

cessively from the standard settings).

8 --- Maintenance / Spare parts

For safety reasons, clear the unit opening the

switch QS1 before performing any maintenance

operations

If installed:

AS THE HIROMATIC/MICROFACE FEATURES AUTOMATIC
RESTART (AFTER A SUPPLY INTERRUPTION) IT IS ADVISED

TO DISABLE AUTORESTART AND OPEN THE SWITCH QF1
AND QF2 (IF PRESENT) WHEN PERFORMING ANY MAINTE-

NANCE.

S

EverydaychecktheHiromatic/Microfacereadingsfortemper-
ature and, if shown, ambient relative humidity.

S

The Maintenance Programme described below should be

carried out by a skilled technician, preferably working under

a maintenance contract.

Summary of Contents for Liebert HIROSS TD 06

Page 1: ...SERVICE MANUAL English Italiano Deutsch Français Español Português Cod 272687 Rev 20 12 2005 Issued by T D Service D ...

Page 2: ......

Page 3: ...ct to modification for complete and up to date information the user should always consult the manual supplied with the machine Index 1 Preliminary operations pag 1 1 1 Foreword pag 1 1 2 Check operating limits pag 1 1 3 Check sound pressure levels pag 1 1 4 Site preparation pag 1 1 5 Conditioner inspection pag 1 1 6 Transport pag 1 1 7 Positioning of air conditioner pag 1 1 8 Service area pag 1 2 ...

Page 4: ...side 2 Mounting For a correct installation proceed as follows S Apply an insulating anti vibration rubber between the unit and the wall see Fig 4 S Before installing the unit open the integrated ducts for the air distribution fins in the openings of the rear panel as indi cated in the figure 1 2 S Secure the unit to the wall with 6 6 fasteners flat head type with washer and nut on the indoor side ...

Page 5: ...ic The below se quence explains with the assistance of Fig 5 Operation dia gram how the unit operates see also Fig 7 Refrigerating circuit 1 The temperature sensor 1 positioned inside the condi tioned room informs the control about the condition of the return air 2 The control compares the information received with the set values of Set Point min inner temperature and Propor tional Band and differ...

Page 6: ...ing to the value set for the dead band compared to the standard setting consequently reducing the power con sumption of the heaters and optimizing their operation accord ing to the site requirements Fig b Unit operation with electrical heating Cooling Heating C Cooling and heating unit P Band Dead Band Cooling and heating unit with Dead band Set point Cooling Heating C 1 2 Band 1 2 Band 1 2 Band 1...

Page 7: ...h temperature S low temperature A further general warning is available in the unit equipped with heating signalling the following abnormal condition heater thermostat reset on thermostat Note S An alarm causes the unit to stop and the unit in stand by if available to intervene S A warning does not stop the unit S Both the alarm and the warning activate sight and sound signals S Both the alarm and ...

Page 8: ...hat cannot be con densed from the hose Charge the circuit exclusively with the refrigerant indicated on the identification label Charge the quantity of refrigerant indicated in Tab 1 3 Close the main switch QS1 and position the outer switch on ON 4 Start the compressor 5 The charge operation can be considered finished when keeping the condensation temperature at a steady level 50 C if necessary pa...

Page 9: ...i fini di una completa e aggiornata informazione l utente dovrà consultare il manuale a bordo della macchina Indice 1 Operazioni preliminari pag 1 1 1 Premessa pag 1 1 2 Verifica limiti di funzionamento pag 1 1 3 Verifica livello di pressione sonora pag 1 1 4 Preparazione del sito pag 1 1 5 Ispezione del condizionatore pag 1 1 6 Trasporto pag 1 1 7 Posizionamento del condizionatore pag 1 1 8 Area ...

Page 10: ...nzione ordinaria può essere realizzata dal la parte frontale S Si evitino eventuali ostacoli che possono interferire con i flussi dell aria sul lato esterno dell unità 2 Installazione Per una corretta installazione procedere come segue S Applicare una guarnizione isolante antivibrante tra l unità e la parete ved Fig 4 S Prima di installare l unità aprire i condotti integrati per la di stribuzione ...

Page 11: ...roface la funzione Autotest che esegue un con trollo sequenziale automatico dei componenti quali il compres sore il ventilatore le resistenze la serranda Freecooling gli al larmi e gli avvisi Tutto questo si traduce in una forte riduzione del tempo necessario alla messa in servizio dell unità all elimi nazione di qualsiasi controllo manuale e all esecuzione di un check veloce dei componenti fondam...

Page 12: ... basa su una regolazione a 1 gradino sia per quanto riguarda il riscalda mento elettrico che per il raffreddamento meccanico con com pressore Il controllo ne gestisce tutti i ritardi di attivazione del compressore come si è visto nel caso precedente al fine di ga rantirne il corretto funzionamento e allungarne il più possibile la vita operativa 6 2 2 Banda morta In questa versione moltoimportante ...

Page 13: ...1 Allarme generale priorità superiore comprendente S bassa pressione compressore S alta pressione compressore reset sul pressostato S guasto sensore S guasto memoria S guasto ventilatore 2 Avviso generale priorità inferiore comprendente S alta temperatura S bassa temperatura E presente nell unità dotata di riscaldamento elettrico un ulte riore Avviso generale per segnalare la seguente condizione a...

Page 14: ...ile collegare il cilindro di carica sulla linea di liquido del circuito Evacuare dal tubo stesso gli in condensabili Caricare il circuito esclusivamente con il refrigerante indicato nella targa di identificazione Caricare la quantità di refrigerante indicata in Tab 1 3 Chiudere l interruttore principale QS1 e posizionare l inter ruttore esterno su ON 4 Avviare il compressore 5 L operazione di cari...

Page 15: ...eliefertes Handbuch des Gerätes Inhaltsverzeichnis 1 Vorbereitende Maßnahmen Seite 1 1 1 Vorbemerkung Seite 1 1 2 Überprüfung der Betriebsgrenzen Seite 1 1 3 Überprüfung des Schalldruckpegels Seite 1 1 4 Vorbereitung Anbringungsort Seite 1 1 5 Überprüfung des Klimagerätes Seite 1 1 6 Transport Seite 1 1 7 Anbringungsort Seite 1 1 8 Wartungsbereich Seite 1 2 Geräte Montage Seite 1 3 Elektrische Ans...

Page 16: ...betriebsschädigenden Um gebung ausgesetzt wird z B ätzende Dämpfe S Das Gerät ist so anzubringen dass in der zu klimatisieren den Umgebung ein optimaler Luftaustausch gesichert ist um so genannte Totzonen zu vermeiden 1 8 Wartungsbereich Um das Gerät ist ein Wartungsbereich zu belassen vgl Fig 2 S Sämtliche ordentliche Wartungen können von der Front seite aus vorgenommen werden S Eventuelle Hinder...

Page 17: ...ngelaufen ist und durchführen folgen der Kontrollen S Prüfe dass die Ventilatoren korrekt funktionieren S Sicherstellen dass die Temperatur gewährleistet ist und dass der Kompressor und die Heizregister optional beiBe darf funktionieren S Sicherstellen dass der Geschwindigkeitsregler des Ventila tors des Kondensators den Betrieb des Ventilators kontrol liert vgl Abschnitt 7 Merke Den Hauptschalter...

Page 18: ...g verwaltet alle Aktivierungsverzögerungen zur Ge währleistung des korrekten Betriebs und zur Verlängerung der Lebensdauer Fig a Betrieb des Gerätes nur Kühlung Set Kühlung C Gerät nur Kühlung P Band 6 2 Geräte mit elektrischer Heizung 6 2 1 Regellogik Für Geräte mit Heizung basiert der Regelalgorithmus auf einer Einstellung die sowohl für das elektrische Heizen als auch für das mechanische Kühlen...

Page 19: ...stehenden Alarmkontakte sind 1 Hauptalarm oberste Priorität mit S Niederdruck des Kompressors S Hochdruck des Kompressors Rückstellung auf dem Druckwächter S Defekt des Sensors S Defekt des Speichers S Fehlbetrieb des Ventilators 2 Allgemeiner Hinweis niedere Priorität mit S Hoher Temperatur S Niederer Temperatur Es ist in der Anlage mit elektrischer Heizung eine weitere Mel dung vorhanden die fol...

Page 20: ...e Flüssigkeitslinie des Kältekreises anschließen Aus der Lei tung die nicht kondensierbaren Reste ablaufen lassen Den Kältekreis ausschließlich mit auf dem Hinweisschild aufgeführten Kältemittel füllen Die in Tab 1 angegebenen Kältemittelmengen einfüllen 3 Anschließen des Hauptschalter QS1 und positionieren des Außenschalter auf ON 4 Den Kompressor starten 5 Der Füllvorgang ist beendet wenn bei ko...

Reviews: