1 --- Preliminary operations

1.1 --- Foreword

The following manual describes the installation, operation and

maintenance of Air Conditioners, series

HIWALL TD

06---08---10---14

.

Important:

Also consult the manual for the Microface micropro-

cessor control supplied with the machine (if installed).

1.2 --- Check operating limits

The units are designed to operate within working ranges (see

Tab. 3). These limits are referred to new machines or for those

that have been correctly installed and serviced.

The warranty clauses are nolonger valid for any damage or mal-

function that may occur during or due to operation outside the

application values.

1.3 --- Check sound pressure levels

Tab. 3 shows, for the internal and the external side, the sound

pressure levels of the units in standard configuration, in continu-

ous operation, at 2 m from the front surface of the machine, at

1 m height in free field conditions.

1.4 --- Site preparation

HIWALL TD shall be mounted on a flat vertical surface.

Prepare cut---outs on the wall for air supply and intake, electrical

connections and unit fixing, according to the attached template

(see Fig. 3). Wall cut outs shall be taped or sealed to prevent air

or moisture entering the wall cavity.

1.5 --- Conditioner inspection

On receiving the equipment immediately inspect its condition;

report any damage to the transport company at once.

1.6 --- Transport

S

Always keep the unit vertically upright.

S

If possible transport the unit using a fork lift truck; otherwise

use a crane with belts or cables, avoiding the exerting of

pressure on the top edges of the packing.

S

Unpack the unit as close as possible to its installation posi-

tion. Once unpacked, avoid stress being transmitted to its

internal components.

S

For lifting the unit, the eyebolts available as accessory can

be used.

Attention:

--- use eyebolts with thread M10;

--- screw the eyebolt completely;

--- always use 4 eyebolts at the same time.

1.7 --- Positioning of air conditioner

S

The air Conditioner shall be installed in any environment not

affected by chemical agents (i.e. acid vapours).

S

Position the air conditioner so as to optimise the indoor air

distribution and avoid hot spots.

1.8 --- Service area

The unit must be provided with a suitable Service Area, as fol-

lows (see Fig. 2):

S

All

ordinary maintenance

can be performed from the front.

S

Avoid possible obstacles hindering the air flows on the unit

outer side.

2 --- Mounting

For a correct installation proceed as follows:

S

Apply an insulating anti---vibration rubber between the unit

and the wall (see Fig. 4).

S

Before installing the unit open the integrated ducts for the air

distribution (fins) in the openings of the rear panel, as indi-

cated in the figure.

1

2

S

Secure the unit to the wall with 6+6 fasteners, flat---head

type with washer and nut on the indoor side (see Fig. 3).

Holes or scxrew anchors for the fixing are suitable as dic-

tated by the wall constructions.

S

Seal the external boundary of the unit as preference (see

Fig. 4).

S

To create stable indoor conditions make sure that the room

is airtight by sealing all gaps, cable entries, etc.

3 --- Electrical connections

3.1 --- Cautions

Before performing any operations on the electric parts, make

sure that:

S

all electrical components are undamaged;

S

all terminal screws are tight;

S

the supply voltage and frequency are as indicated on the

unit;

S

the automatic switches

QF1

and

QF2

(if present)are in open

position (OFF);

S

all components are isolated.

3.2 --- Electrical supply

Let the electrical power supply cable (not powered) pass

through the holes placed in the back panel of the air conditioner

(see Fig. 3).

Caution:

Use screened cables for high voltage power supply,

of a suitable cross section area, and route them to the electrical

panel. Use copper conductors only.

Connect the power supply cable to the main switch QF1 inside

the electrical panel. Connect the earth cable to the yellow---

green clamp. The alarm contacts available in the different ver-

sions are located inside the electrical panel. For the alarms de-

scription see chapter 6.5 and manual of the installation control.

3.3 --- Fast fittings

(upon request, only)

Through the fast fittings, supplied upon request only, it is pos-

sible to connect and start the unit without having to install any

power, signal and mains cable inside the machine. True fast

connections are thus achieved, that can be carried out safely

with a significant saving in the installation time.

3.4 --- User interface

The standard control system on HIWALL TD is based on the Mi-

croface microprocessor board: it is inside the electric board and

can be connected with the user interface (remote display) that

can be positioned inside the room as wished. The user interface

(remote display), when installed, in a painted metal box, is con-

nected with the conditioner through a Hirobus multi---pole

screened cable, standard supplied.

The user interface can be Microface type (with 3---digit display)

or Hiromatic type (optional, with graphic display and extended

keypad).

Summary of Contents for Liebert HIROSS TD 06

Page 1: ...SERVICE MANUAL English Italiano Deutsch Français Español Português Cod 272687 Rev 20 12 2005 Issued by T D Service D ...

Page 2: ......

Page 3: ...ct to modification for complete and up to date information the user should always consult the manual supplied with the machine Index 1 Preliminary operations pag 1 1 1 Foreword pag 1 1 2 Check operating limits pag 1 1 3 Check sound pressure levels pag 1 1 4 Site preparation pag 1 1 5 Conditioner inspection pag 1 1 6 Transport pag 1 1 7 Positioning of air conditioner pag 1 1 8 Service area pag 1 2 ...

Page 4: ...side 2 Mounting For a correct installation proceed as follows S Apply an insulating anti vibration rubber between the unit and the wall see Fig 4 S Before installing the unit open the integrated ducts for the air distribution fins in the openings of the rear panel as indi cated in the figure 1 2 S Secure the unit to the wall with 6 6 fasteners flat head type with washer and nut on the indoor side ...

Page 5: ...ic The below se quence explains with the assistance of Fig 5 Operation dia gram how the unit operates see also Fig 7 Refrigerating circuit 1 The temperature sensor 1 positioned inside the condi tioned room informs the control about the condition of the return air 2 The control compares the information received with the set values of Set Point min inner temperature and Propor tional Band and differ...

Page 6: ...ing to the value set for the dead band compared to the standard setting consequently reducing the power con sumption of the heaters and optimizing their operation accord ing to the site requirements Fig b Unit operation with electrical heating Cooling Heating C Cooling and heating unit P Band Dead Band Cooling and heating unit with Dead band Set point Cooling Heating C 1 2 Band 1 2 Band 1 2 Band 1...

Page 7: ...h temperature S low temperature A further general warning is available in the unit equipped with heating signalling the following abnormal condition heater thermostat reset on thermostat Note S An alarm causes the unit to stop and the unit in stand by if available to intervene S A warning does not stop the unit S Both the alarm and the warning activate sight and sound signals S Both the alarm and ...

Page 8: ...hat cannot be con densed from the hose Charge the circuit exclusively with the refrigerant indicated on the identification label Charge the quantity of refrigerant indicated in Tab 1 3 Close the main switch QS1 and position the outer switch on ON 4 Start the compressor 5 The charge operation can be considered finished when keeping the condensation temperature at a steady level 50 C if necessary pa...

Page 9: ...i fini di una completa e aggiornata informazione l utente dovrà consultare il manuale a bordo della macchina Indice 1 Operazioni preliminari pag 1 1 1 Premessa pag 1 1 2 Verifica limiti di funzionamento pag 1 1 3 Verifica livello di pressione sonora pag 1 1 4 Preparazione del sito pag 1 1 5 Ispezione del condizionatore pag 1 1 6 Trasporto pag 1 1 7 Posizionamento del condizionatore pag 1 1 8 Area ...

Page 10: ...nzione ordinaria può essere realizzata dal la parte frontale S Si evitino eventuali ostacoli che possono interferire con i flussi dell aria sul lato esterno dell unità 2 Installazione Per una corretta installazione procedere come segue S Applicare una guarnizione isolante antivibrante tra l unità e la parete ved Fig 4 S Prima di installare l unità aprire i condotti integrati per la di stribuzione ...

Page 11: ...roface la funzione Autotest che esegue un con trollo sequenziale automatico dei componenti quali il compres sore il ventilatore le resistenze la serranda Freecooling gli al larmi e gli avvisi Tutto questo si traduce in una forte riduzione del tempo necessario alla messa in servizio dell unità all elimi nazione di qualsiasi controllo manuale e all esecuzione di un check veloce dei componenti fondam...

Page 12: ... basa su una regolazione a 1 gradino sia per quanto riguarda il riscalda mento elettrico che per il raffreddamento meccanico con com pressore Il controllo ne gestisce tutti i ritardi di attivazione del compressore come si è visto nel caso precedente al fine di ga rantirne il corretto funzionamento e allungarne il più possibile la vita operativa 6 2 2 Banda morta In questa versione moltoimportante ...

Page 13: ...1 Allarme generale priorità superiore comprendente S bassa pressione compressore S alta pressione compressore reset sul pressostato S guasto sensore S guasto memoria S guasto ventilatore 2 Avviso generale priorità inferiore comprendente S alta temperatura S bassa temperatura E presente nell unità dotata di riscaldamento elettrico un ulte riore Avviso generale per segnalare la seguente condizione a...

Page 14: ...ile collegare il cilindro di carica sulla linea di liquido del circuito Evacuare dal tubo stesso gli in condensabili Caricare il circuito esclusivamente con il refrigerante indicato nella targa di identificazione Caricare la quantità di refrigerante indicata in Tab 1 3 Chiudere l interruttore principale QS1 e posizionare l inter ruttore esterno su ON 4 Avviare il compressore 5 L operazione di cari...

Page 15: ...eliefertes Handbuch des Gerätes Inhaltsverzeichnis 1 Vorbereitende Maßnahmen Seite 1 1 1 Vorbemerkung Seite 1 1 2 Überprüfung der Betriebsgrenzen Seite 1 1 3 Überprüfung des Schalldruckpegels Seite 1 1 4 Vorbereitung Anbringungsort Seite 1 1 5 Überprüfung des Klimagerätes Seite 1 1 6 Transport Seite 1 1 7 Anbringungsort Seite 1 1 8 Wartungsbereich Seite 1 2 Geräte Montage Seite 1 3 Elektrische Ans...

Page 16: ...betriebsschädigenden Um gebung ausgesetzt wird z B ätzende Dämpfe S Das Gerät ist so anzubringen dass in der zu klimatisieren den Umgebung ein optimaler Luftaustausch gesichert ist um so genannte Totzonen zu vermeiden 1 8 Wartungsbereich Um das Gerät ist ein Wartungsbereich zu belassen vgl Fig 2 S Sämtliche ordentliche Wartungen können von der Front seite aus vorgenommen werden S Eventuelle Hinder...

Page 17: ...ngelaufen ist und durchführen folgen der Kontrollen S Prüfe dass die Ventilatoren korrekt funktionieren S Sicherstellen dass die Temperatur gewährleistet ist und dass der Kompressor und die Heizregister optional beiBe darf funktionieren S Sicherstellen dass der Geschwindigkeitsregler des Ventila tors des Kondensators den Betrieb des Ventilators kontrol liert vgl Abschnitt 7 Merke Den Hauptschalter...

Page 18: ...g verwaltet alle Aktivierungsverzögerungen zur Ge währleistung des korrekten Betriebs und zur Verlängerung der Lebensdauer Fig a Betrieb des Gerätes nur Kühlung Set Kühlung C Gerät nur Kühlung P Band 6 2 Geräte mit elektrischer Heizung 6 2 1 Regellogik Für Geräte mit Heizung basiert der Regelalgorithmus auf einer Einstellung die sowohl für das elektrische Heizen als auch für das mechanische Kühlen...

Page 19: ...stehenden Alarmkontakte sind 1 Hauptalarm oberste Priorität mit S Niederdruck des Kompressors S Hochdruck des Kompressors Rückstellung auf dem Druckwächter S Defekt des Sensors S Defekt des Speichers S Fehlbetrieb des Ventilators 2 Allgemeiner Hinweis niedere Priorität mit S Hoher Temperatur S Niederer Temperatur Es ist in der Anlage mit elektrischer Heizung eine weitere Mel dung vorhanden die fol...

Page 20: ...e Flüssigkeitslinie des Kältekreises anschließen Aus der Lei tung die nicht kondensierbaren Reste ablaufen lassen Den Kältekreis ausschließlich mit auf dem Hinweisschild aufgeführten Kältemittel füllen Die in Tab 1 angegebenen Kältemittelmengen einfüllen 3 Anschließen des Hauptschalter QS1 und positionieren des Außenschalter auf ON 4 Den Kompressor starten 5 Der Füllvorgang ist beendet wenn bei ko...

Reviews: