44
Section 8: Parameter Menu
User Instructions
MAN-02-04-60-0351-EN Rev. 3
Febraury 2019
Parameter Menu
Table 13.
Binary Inputs Parameter Group (2)
Menu
Item
Sub Menu
Item
Poss. Setting
Notes / Comments
P9.1
Binary
Input
Input 1
31: Intermediate
position1
Approach intermediate position 1 (P8.1) in
REMOTE mode (fix position approach). There is no
repositioning upon reaching the intermediate
position within the hysteresis (see P8.6). Higher
priority than intermediate position 2, 3 and 4
32: Intermediate
position2
As intermediate position 1, but with higher priority
than intermediate positions 3 and 4
33: Intermediate
position3
As intermediate position 1, but with higher priority
than intermediate position 4
34: Intermediate
position4
As intermediate position 1, but with lowest priority
35: Emergency
position
Approach emergency position (P 8.5). As
intermediate position 1, but with higher priority than
intermediate positions 1, 2
36: Intermediate
position1 inv.
As Intermediate position 1, but active low
37: Intermediate
position2 inv.
As Intermediate position 2, but active low
38: Intermediate
position3 inv.
As Intermediate position 3, but active low
39: Intermediate
position4 inv.
As Intermediate position 4, but active low
40: Emergency
position inv.
As Emergency position, but active low
41: Travel Open
reserved for future use
42: Travel Close
reserved for future use
43: Travel Open
inv.
reserved for future use
44: Travel Close
inv.
reserved for future use
45: Failsafe lock
reserved for future use (only for Failsafe actuators)
46: Failsafe lock
inv.
reserved for future use (only for Failsafe actuators)
P9.2 Bin. Input Input 2
see Input 1
P9.3 Bin. Input Input 3
see Input 1
P9.4 Bin. Input Input 4
see Input 1
P9.5 Bin. Input Input 5
see Input 1