80
Section 17: Technical Data and Certifications
Technical Data and Certifications
User Instructions
MAN-02-04-60-0351-EN Rev. 3
Febraury 2019
17.3
Analog Inputs
Table 36.
Input 1: Setpoint Value
Characteristic
Value
Current range:
0-25mA
Resolution:
14Bit
Accuracy:
0,5%
Input resistance:
60 Ω
Analog input 1 is electrically isolated from the rest of the electronic system.
Table 37.
Input 2: External Actual Value
Only in Conjunction with the PID Controller
Characteristic
Value
Current range:
0-20,8mA
Resolution:
12Bit
Accuracy:
0,5%
Input resistance:
120 Ω
Jumper JP6 can be used to switch analog input 2 from a passive input (default) to an input
with internal 24 V power supply (for 4. . . 20 mA, two-wire transmitters).
NOTE:
The analog input 2 is referenced to common of the electronic system and the auxiliary
power supply.
17.4
Analog Output
Table 38.
Analog Output
Characteristic
Value
Current range:
0-20,8mA
Resolution:
12Bit
Accuracy:
0,5%
Input resistance:
600 Ω