Section 8: Parameter Menu
User Instructions
MAN-02-04-60-0351-EN Rev. 3
Febraury 2019
Parameter Menu
8.7
Parameter Group: Position
In addition to OPEN and CLOSED end positions, you may define intermediate positions.
These can be used as feedback signals for the binary outputs or as target value for fix
position approach.
CAUTION: CHANGING END POSITIONS
If you change the end positions (see Section 7.1, intermediate positions are retained
percentage-wise, i.e., the absolute positions of the intermediate positions change.
Table 11.
Position Parameter Group
Menu Item
Sub Menu
Item
Poss.
Setting
Notes / Comments
P8.1
Position
Intermed.
pos.1
TEACHIN
0 - 100%
Position value of intermediate position 1
P8.2
Position
Intermed.
pos.2
TEACHIN
0 - 100%
see above
P8.3
Position
Intermed.
pos.3
TEACHIN
0 - 100%
see above
P8.4
Position
Intermed.
pos.4
TEACHIN
0 - 100%
see above
P8.5
Position
Emerg.
position
TEACHIN
0 - 100%
Position value of the emergency position.
P8.6
Position
Hysteresis
0,1 - 10,0%
Hysteresis range of intermediate positions. Within this
hysteresis, no repositioning occurs upon reaching the
intermediate positions (option: fix position approach).
Furthermore, the output functions for position =
intermediate position are active within this range (see
P10.1 . . . ).
8.8
Parameter Group: Binary Inputs
The controller is equipped with 5 freely configurable binary inputs. Please find further
information on technical data of the binary inputs in Section 17.2. Binary inputs are also
effective during actuator control via Profibus (option).
Default binary inputs are as follows:
•
Input 1: OPEN
•
Input 2: CLOSED
•
Input 3: STOP
•
Input 4: EMERGENCY OPEN
•
Input 5: EMERGENCY CLOSED