39
Section 8: Parameter Menu
User Instructions
MAN-02-04-60-0351-EN Rev. 3
February 2019
Parameter Menu
CAUTION: NOTE TRAVEL LIMITS
When installing the actuator on an gear or a thrust unit, please take into account the limits
and factors of the gear / thrust unit at parametrization.
CAUTION: SET LIMITS CORRECTLY
When using end limit switch off by torque, the end position limit must be set before
reaching the torque limit. Accordingly, the actuator will only signal the final end position
if the configured torque and the associated end position are reached. If the end position is
not reached, a torque error is reported (see Section 6.2.2)
8.2
Parameter Group: Torque
If no torque was specified with the order, the actuator is supplied from the factory with the
maximum configurable torque.
Table 6.
Torque Parameter Group
Menu Item
Sub Menu
Item
Poss.
Setting
Notes / Comments
P2.1 Torque
Open
8 - 32Nm
2)
Switch-off torque in OPEN direction
CAUTION: The range can be restricted via menu
item P2.3.
P2.2
Torque
Close
8 - 32Nm
2)
As P2.1, but in CLOSED direction.
P2.3 Torque
Torque limit
8 - 32Nm
2)
Torque to protect the valve, the transmission, or the
thrust unit.
This value limits the setting of parameters P2.1 and
P2.2 to prevent an erroneous increase above the
allowed value of these two parameters.
P2.4 Torque
Latching
Off (0)
Unassigned in RTS Compact Multi-Turn CM series
2)
representative for CM03
CAUTION: NOTE GEAR AND THRUST UNITS
When installing the actuator on an additional gear, please take into account the
corresponding values of the gear / thrust unit as you enter the actuator parameters.
To achieve an effective output torque (incl. gear) / output power (including thrust unit)
ratio, the factor gear/thrust unit must be considered.