Procedure
Have the following tools on hand before you begin these steps: standard Phillips screwdriver,
nut driver, torque wrench, multimeter, and lugs.
1. Locate the target power input cable’s terminals at the branch circuit or power
distribution unit. Open the external circuit breakers that provide DC feed power to
the chassis.
2. Lock and tagout the circuit breakers on the branch circuit or power distribution
unit.
3. Using the appropriate tool, carefully remove the plastic covering over the terminal
blocks.
4. Confirm that there is no power to the chassis lug bolts. Using a multimeter,
measure between the two lugs and then measure between the chassis ground and
each lug. If the DC potential is 3.0VDC or less, then power is not present.
5. Attach the DC power cables (input and return) to the dual lug bolts on each chassis
power feed.
6. Using a torque wrench, tighten the nuts with a recommended torque setting of
35.5 to 38.5 inch-pounds. Make sure all DC leads are fastened securely.
7. Replace the plastic cover over the terminal blocks.
Cables may or may not be preinstalled at the branch circuit or power distribution unit.
If the DC power cables are not connected to the branch circuit or power distribution unit,
connect the power cables to the chassis before connecting the DC power cables to the
external power source.
If the DC power cables are connected to the branch circuit or power distribution unit, a
qualified service person must confirm that the power to the cables is terminated (off) before
continuing the steps to attach the cables to the PEMs.
In either case, use a multimeter to check the PEM end of the terminals to confirm there is no
power present.
Summary of Contents for AXP640-AC2-110VAC
Page 8: ...AXP640 Installation and Use 6806800M24E Contents 8 Contents Contents ...
Page 10: ...AXP640 Installation and Use 6806800M24E 10 List of Tables ...
Page 26: ...Platform Architecture AXP640 Installation and Use 6806800M24E 26 ...
Page 46: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24E 46 Figure 2 14 AC Inlet 220V ...
Page 52: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24E 52 ...
Page 76: ...Site Preparation AXP640 Installation and Use 6806800M24E 76 ...
Page 86: ...AXP640 Operations AXP640 Installation and Use 6806800M24E 86 ...
Page 110: ...AXP640 Shelf Installation AXP640 Installation and Use 6806800M24E 110 ...
Page 138: ...FRU Installation AXP640 Installation and Use 6806800M24E 138 ...
Page 189: ......