Shelf Management Alarm Module
AXP640 Installation and Use (6806800M24E
)
148
The deltaT set point is calculated as follows:
For ambient air temperatures at or below 25°C (default T1), the deltaT set point is set to 20°C
(default S1). For ambient air temperatures at or above 55°C (default T2), the deltaT set point is
set to 10°C (default S2). For ambient air temperatures between T1 and T2, the deltaT set point
is calculated using the following algorithm:
Set Point
S1
S2
T1
T2
Inlet Air Temperature
S2 - S1
T2 - T1
S1 +
(T
inlet
- T1)