Volume Conversion Device EK220
86
©
Elster GmbH
4.4.2 FE230 Function Expansion with modem
F
Connection see Chap. 5.6.2
The FE230 is a battery-powered function expansion with integral modem.
For this application extended parameterization of the device via the optical interface is r e-
quired. Special parameter files are available for this which are installed with the "Win-
PADS" program and which can also be loaded into the device using the program.
After the parameterising process with "Md.S2 = 6", the settings for the read -out time win-
dow should be made under the interface list (
®
3.13).
- Md.S2 = 6
Without modem control. The modem accepts the call automati-
cally. Battery operation is possible. The EK220 controls the mo-
dem and the call acceptance. Num.T is activated.
- Bd.S2 = 19200 Baud rate 19200 Bd
- TypS2 = RS485 Type of interface 2: RS485
- BusS2 = 0
No bus mode.
- Num.T = ...
Num.T is not activated.
!
After the parameterisation process particularly the settings for the readout time window
must be adjusted under the interface list (
®
3.13), because the battery service life of
the FE230 crucially depends on them.
4.4.3 Devices with RS485 interface, without modem (also FE260 without mo-
dem)
F
For this applications the EK220 needs an external power supply.
F
Connection see Chap. 5.6.1, page 95.
For the connection of a device with RS485 interface without a modem, the following se t-
tings must be made under the interface list (
®
3.13):
- Md.S2 = 5
No modem control by the EK220, without control signals, baud
rate selection possible
- Bd.S2 = 300
With application of baud rate selection according to IEC 62056-21
(procedure as for the optical interface)
1
or
= 19200 Baud rate selection bypassed
- TypS2 = RS485
Type of interface 2: RS485
- BusS2 = 0
No bus mode.
4.4.4 EK220 connected to RS485-Bus (real RS485)
F
For this applications the EK220 needs an external power supply.
F
Connection see Chap. 5.6.1, page 95.
1
The set baud rate is only used briefly for initiating the data interchange. The actual baud
rate for transmitting the useful data is increased automatically to 9600 Bd.
Summary of Contents for EK220
Page 2: ...Volume Conversion Device EK220 2 Elster GmbH ...
Page 110: ...Volume Conversion Device EK220 110 Elster GmbH A 2 Approval for Ex Zone ...
Page 111: ...Volume Conversion Device EK220 Elster GmbH 111 ...
Page 112: ...Volume Conversion Device EK220 112 Elster GmbH ...
Page 113: ...Volume Conversion Device EK220 Elster GmbH 113 ...
Page 114: ...Volume Conversion Device EK220 114 Elster GmbH ...