Volume Conversion Device EK220
©
Elster GmbH
85
4.4 Applications for Interface 2 as RS485
4.4.1 FE260 Function Expansion
F
Connection see Chap. 5.6.1, page 95
The FE260 is a mains-powered function expansion incl. Ex isolation and supply for the
EK220. It has may have alternatively an integral modem or a connection for a comme r-
cially available modem.
For the connection of an FE260 with integral or separately connected modem, the follo w-
ing settings should be made under the interface list (
®
3.13):
- Md.S2 =
3
With modem control by "return messages"
via data lines,
without baud rate selection. Num.T is activated.
or
=
5
*
Without modem control
. Either the modem accepts the call
automatically or another device is connected to the FE260 (no
modem). Num.T is not activated.
- Bd.S2 = 19200 * Baud rate 19200 Bd (or lower, depending on the device con-
nected to the FE260)
- TypS2 = RS485
Type of interface 2: RS485
- BusS2 = 0
No bus mode.
- Num.T = ...
Num.T is only activated with Md.S2 = 3.
Possible values are dependent on the modem used, e.g.:
- Standard modem (Insys) integrated in FE260 ............ 2 to 9
- ISDN modem (Insys) integrated in FE260 .................. 2 to 9
- GSM modem (Wavecom) integrated in FE260 .......... 1 to 9
- Separate GSM modem Siemens M20T or TC35T ...... 1
- Separate analogue modem EM200 or Insys Onbit ..... 2 to 9
* Normally, modems do not execute any baud rate selection so that with Md.S2 = "5" the
values under the addresses 02:708 (Bd.S2) and 02:709 must be equal.
For the connection of a device with baud rate selection, the starting baud rate (normally
300 Bd) must be set under the Bd.S2 (address 02:708) and the baud rate identification
under address 02:709.
Summary of Contents for EK220
Page 2: ...Volume Conversion Device EK220 2 Elster GmbH ...
Page 110: ...Volume Conversion Device EK220 110 Elster GmbH A 2 Approval for Ex Zone ...
Page 111: ...Volume Conversion Device EK220 Elster GmbH 111 ...
Page 112: ...Volume Conversion Device EK220 112 Elster GmbH ...
Page 113: ...Volume Conversion Device EK220 Elster GmbH 113 ...
Page 114: ...Volume Conversion Device EK220 114 Elster GmbH ...