Volume Conversion Device EK220
©
Elster GmbH
65
3.12 Output list
AD
Designation / value
Unit
Access Address DC
Md.O1 Mode
for Output 1
-
S
1:605
7
SC.O1 Source
for Output 1
-
S
1:606
21
cp.O1 Cp value
for Output 1
1/m3
S
1:611
8
SpO1
Status pointer for Output 1
-
S
1:607
8
Md.O2 Mode
for Output 2
-
S
2:605
7
SC.O2 Source
for Output 2
-
S
2:606
21
cp.O2 Cp value
for Output 2
1/m3
S
2:611
8
SpO2
Status pointer for Output 2
-
S
2:607
8
Md.O3 Mode
for Output 3
-
S
3:605
7
SC.O3 Source
for Output 3
-
S
3:606
21
cp.O3 Cp value
for Output 3
1/m3
S
3:611
8
SpO3
Status pointer for Output 3
-
S
3:607
8
Md.O4 Mode
for Output 4
-
S
4:605
7
SC.O4 Source
for Output 4
-
S
4:606
21
cp.O4 Cp value
for Output 4
1/m3
S
4:611
8
SpO4
Status pointer for Output 4
-
S
4:607
8
(Legends: see page 22)
The function of the outputs can be set with the values described here. The ex -works stan-
dard setting is:
-
Output 1:
Pulse output
VbT
(total volume at base conditions), 1 pulse per m
3
;
changes to the settings only possible with open supplier's lock.
-
Output 2:
Pulse output
VmT
(total actual volume), 1 pulse per m
3
;
changes to the settings only possible with open supplier's lock.
-
Output 3:
Status output alarm or warning, logic active;
Changes to the settings only possible with open supplier's lock.
-
Output 4:
Pulse output
VbT
(total volume at base conditions), 1 pulse per m
3
;
changes to the settings only possible with open supplier's lock.
With the aid of the WinPADS Parameterization Software the access rights (
®
2.4) men-
tioned here can be changed for each output with an appropriately open lock. In this r e-
spect there are the following alternatives:
-
Changes to the settings only possible subject to the calibration lock.
-
Changes to the settings possible subject to the supplier's and calibration locks.
-
Changes to the settings possible subject to the customer's, supplier's and calibration locks.
Md.O1 ... Md.O4 Mode for Outputs 1...4
The four signal outputs of the EK220 can be set for various functions. The basi c func-
tion is defined with the mode
Md.A...
Depending on this, the source (
SC.A...,
see be-
low), the cp value (
cp.A...,
see below) or the status pointer (
SpO...
, see below) must
also be parameterised, where necessary, for the relevant output.
In the following table, apart from the setting possibilities for
Md.A
... it is shown for each
setting whether
SC.A...
,
cp.A...
or
SpO...
must be parameterised.
Summary of Contents for EK220
Page 2: ...Volume Conversion Device EK220 2 Elster GmbH ...
Page 110: ...Volume Conversion Device EK220 110 Elster GmbH A 2 Approval for Ex Zone ...
Page 111: ...Volume Conversion Device EK220 Elster GmbH 111 ...
Page 112: ...Volume Conversion Device EK220 112 Elster GmbH ...
Page 113: ...Volume Conversion Device EK220 Elster GmbH 113 ...
Page 114: ...Volume Conversion Device EK220 114 Elster GmbH ...