78
Temperature parameter settings
Sensor with Cala KNX display
• Version: 13.03.2017 • Technical changes and errors excepted.
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
2-point-control (only level 2):
2-point-control is used for systems which are only set to ON or OFF.
Enter the hysteresis that prevents frequent on/off switching of temperatures in the
threshold range.
If separate control variables are used, select whether the control variable of the 2nd
level is a 1 bit object (on/off) or an 8 bit object (on with percentage/off).
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
8.4.
Summer Compensation
With the summer compensation the target value for the room temperature can auto-
matically be adapted by cooling at higher outdoor temperatures. The objective is to
prevent a too great a difference between indoor and outdoor temperature in order to
keep the energy consumption low.
Maximum control variable is reached
at setpoint/actual difference of (in °C)
Cooling ceiling: 5
Reset time (in min.)
Cooling ceiling: 30
When blocked, the control variable shall
• not be sent
• send a specific value
Value (in %)
(if a value is sent)
0...100
Control type
is determined at a higher level for common
variables
•
2-point-control
Hysteresis (in 0.1°C)
0...100; 20
Control variable is a
• 1 bit object
• 8 bit object
Value (in %)
(for 8 bit object)
0...100
When blocked, the control variable shall
• not be sent
• send a specific value
Value (in %)
(if a value is sent)
0...100