71
Temperature parameter settings
Sensor with Cala KNX display
• Version: 13.03.2017 • Technical changes and errors excepted.
General setpoint values
You may enter separate setpoint values for each mode or use the comfort setpoint as
a basic value.
If you are using the control for both heating
and
cooling, you may also select the set-
ting "separately with switching object". Systems used for cooling in summer and for
heating in winter can thus be switched from one to the other.
If you are using the basic value, only the deviation from the comfort setpoint value is
listed for the other modes (e.g, 2°C less for standby mode).
The
increment
for the setpoint changes is predefined. Whether the change only re-
mains temporarily active (not saved) or is also retained after power supply restoration
(and programming), is specified in the first section of "General control". This also ap-
plies to a comfort extension.
The control may be reset to comfort mode from eco mode, which is used as night
mode, via the comfort extension. This allows the user to maintain the comfort setpoint
value for a longer time, e.g. when having guests. The duration of this comfort exten-
sion period is set. After the comfort extension period expires, the system returns to eco
mode.
Type of control
• Single level heating
• Dual-level heating
• Single-level cooling
• Dual-level cooling
• Single-level h single-level cooling
• Dual-level h single-level cooling
• Dual-level h dual-level cooling
Setting the setpoint values
• with separate setpoint values with
Switching object
• with separate setpoint values without
Switching object
• with comfort setpoint as a basis with
Switching object
• with comfort setpoint as a basis without
Switching object
Behaviour of the switching object at value
(with switching object)
• 0 = Heating | 1 = Cooling
• 1 = Heating | 0 = Cooling
Value of the switching object after reset
(with switching object)
0 • 1
Increment for setpoint changes
(in 0.1 °C)
1… 50; 10
Comfort extension time in seconds
(can only be activated from eco mode)
1…36000; 3600