33
Transfer protocol
Sensor with Cala KNX display
• Version: 13.03.2017 • Technical changes and errors excepted.
198 Humidity threshold value 3:
Switching output block
Input
-WC-
[1.1] DPT_Switch
1 bit
199 Humidity threshold value 4:
Absolute value
Input/
Output
RWCT [9,007] DPT_Val-
ue_Humidity
2 bytes
200 Humidity threshold value 4: (1:+ | 0:-) Input
-WC-
[1.1] DPT_Switch
1 bit
201 Humidity threshold value 4: Delay
from 0 to 1
Input
-WC-
[7.005] DPT_-
TimePeriodSec
2 bytes
202 Humidity threshold value 4: Delay
from 1 to 0
Input
-WC-
[7.005] DPT_-
TimePeriodSec
2 bytes
203 Humidity threshold value 4:
Switching output
Output
R-CT
[1.1] DPT_Switch
1 bit
204 Humidity threshold value 4:
Switching output block
Input
-WC-
[1.1] DPT_Switch
1 bit
Dew point, coolant monitoring
(objects 221-229)
for Cala KNX AQS/TH (item no. 70603, 70608), Cala KNX TH (item no. 70602, 70608)
221 Dewpoint: Measured value
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 bytes
222 Coolant temp.: Threshold value
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 bytes
223 Coolant temp.: Actual value
Input
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
224 Coolant temp.: Offset change
(1:+ | 0:-)
Input
-WC-
[1.1] DPT_Switch
1 bit
225 Coolant temp.: Offset current
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 bytes
226 Coolant temp.: Switching delay from
0 to 1
Input
-WC-
[7.005] DPT_-
TimePeriodSec
2 bytes
227 Coolant temp.: Switching delay from
1 to 0
Input
-WC-
[7.005] DPT_-
TimePeriodSec
2 bytes
228 Coolant temp.: Switching output
Output
R-CT
[1.1] DPT_Switch
1 bit
229 Coolant temp.: Switching output
block
Input
-WC-
[1.1] DPT_Switch
1 bit
Absolute humidity
(objects 231-232)
for Cala KNX AQS/TH (item no. 70603, 70608), Cala KNX TH (item no. 70602, 70607)
231 Absolute humidity [g/kg]
Output
R-CT
[14.5] DPT_Val-
ue_Amplitude
4 bytes
232 Absolute humidity [g/m³]
Output
R-CT
[14.17] DPT_Val-
ue_Density
4 bytes
Room climate status
(objects 234-235)
for Cala KNX AQS/TH (item no. 70603, 70608), Cala KNX TH (item no. 70602, 70607)
234 Ambient climate status: 1 =
comfortable | 0 = uncomfortable
Output
R-CT
[1.1] DPT_Switch
1 bit
235 Ambient climate status: Text
Output
R-CT
[16.0]
DPT_String_ASCII
14 bytes
No. Text
Function Flags
DPT type
Size
Summary of Contents for Cala KNX AQS/TH