Manual: R1300-X-00-X_EN Release: 1.04 © Elotech GmbH Page 8/20
Display
Parameter
Display
"Process"
„Set“
SEn
Sensor selection
P1 °C
Pt 100,
-50,0...100,0 °C
P1 °F
Pt 100,
-58,0...212,0 °F
P2 °C
Pt 100,
-90,0...205,0 °C
P2 °F
Pt 100,
-130...401 °F
P3 °C
Pt 100,
0,0...300,0 °C
P3 °F
Pt 100,
32...572 °F
P4 °C
Pt 100,
0...400 °C (ex works)
P4 °F
Pt 100,
32...752
°F
P8° C
Pt 100,
0...800
°C
P8 °F
Pt 100,
32...1472
°F
L4 °C
T/C Fe-CuNi (L),
0...400
°C
L4 °F
T/C Fe-CuNi (L),
32...752
°F
L8 °C
T/C Fe-CuNi (L),
0...800
°C
L8 °F
T/C Fe-CuNi (L),
32...1472
°F
J8 °C
T/C Fe-CuNi (J),
0...800
°C
J8 °F
T/C Fe-CuNi (J),
32...1472
°F
n1 °C
T/C NiCr-Ni (K),
0...1200
°C
n1 °F
T/C NiCr-Ni (K),
32...2192
°F
S1 °C
T/C Pt10Rh-Pt (S),
0...1600
°C
S1 °F
T/C Pt10Rh-Pt (S), 32...2912
°F
0 - 20
Current
0...20
mA
4 - 20
Current
4...20 mA
10 dc
Voltage
0...10
V dc
If the Sensor selection is changed, the following parameters will be reset (setting in brackets)
and need to be re-adjusted:
All Setpoints (OFF); ramps (OFF); alarm value (OFF); control sensivity ( 0);
process offset(OFF); lower setpoint limitation (SP.Lo); higher setpoint limitation (SP.Hi).
The following parameters are only valid for standard signal inputs (0...20mA, 4...20mA, 0...10Vdc). The
difference between the bottom end of the display range and the top end must amount to a minimum of
100 units and a maximum of 2000 units. By adjustment of one of the above parameters, the other
in this case will automatically follow.
rA.SP decimal points
0; 1; 2
(ex works: 1)
rA.Hi display range top end
rA.Lo ... 9999
(ex works: 100,0)
rA.Lo display range bottom end
-1999 ... rA.Hi
(ex works: 0,0)
Only version R1300-3:
Sc.Hi higher indication range limitation
valid for the analogue setpoint in- and outputs and
(20mA, 10 VDC)
the analogue process value output.
Sc.Lo lower indication range limitation
valid for the analogue setpoint in- and outputs and
(0/4mA, 0/2 VDC)
the analogue process value output.
The difference between the bottom end of the range and the top end must be an amount to a minimum of
25% percent of the measuring range.
SP.Hi higher setpoint limitation
Valid for the analogue input and the keyboard adjustments.
programming range:
SP.Lo ... top range
(ex works: 400)
SP.Lo lower setpoint limitation
Valid for the analogue input and the keyboard adjustments.
programming range:
bottom range ... SP.Hi (ex works: 0)