Manual: R1300-X-00-X_EN Release: 1.04 © Elotech GmbH Page 15/20
Display
Parameter
Display
"Process"
„Set“
The following parameters apply only to the configuration of 3-point-step-controllers:
P
xp, prop.-band (P)
OFF; 0,1...200,0 %
(ex works: 10,0)
tS
Motor, actuating time
5 ... 800 secs
(ex works: 40)
tn
reset time (I)
0,5 ... 80,0 min.
(ex works: 3,0)
Sd
control sensivity
OFF; 0,1...80,0
units
(ex works: OFF)
OFF; 0,01...8,00
units 1)
OFF; 0,001...0,800
units 2)
Sh
dead band
OFF; 0,1...80,0 units
(ex works: OFF)
OFF; 0,01...8,00
units 1)
OFF; 0,001...0,800
units 2)
on
off
Sh
on
off
Sd
SETPOINT
PROCESS
3-point-step-controllers use PI control action in combination with motor actuators.
It is important, that SH should be several times larger than Sd.
Switching frequency is dependant on the pre-selected feedback values.