Manual: R1300-X-00-X_EN Release: 1.04 © Elotech GmbH Page 12/20
Display
Parameter
Display
"Process"
„Set“
Co.Sb Sensor break
This parameter is only available when the controller is configurated as a
3-point-step-controller. Behaviour in event of sensor break:
OFF
OUT1: off;
OUT2: off
(ex works)
OUT2
OUT1: off
OUT2: on
OUT1
OUT1: on
OUT2: off
LOC
Adjustment lock
OFF
no adjustment lock (ex works)
P C
parameter and configuration levels locked
n.SP1
all parameters apart from SP1 locked (not SP1)
ALL
all parameters locked
All parameters that have been locked with „LOC“ can be
selected and read, but not altered.
This adjustment cannot be changed if the external contact
K2 is closed.
The following parameters are only valid, if the unit is equipped with a serial interface.
Only > version R-1300-2:
Adr
Unit adress
1 .... 255
(ex works: 1)
The computer adresses the unit at this adress.
Each unit has ist own adress.
It is possible to adress 32 units.
For
Data format
7E1
7 data, even, 1 stopbit
7o1
7 data, odd, 1 stopbit
7E2
7 data, even, 2 stopbit
7o2
7 data, odd, 2 stopbit
7n2
7 data, none, 2 stopbit
8E1
8 data, even, 1 stopbit
8o1
8 data, odd, 1 stopbit
8n1
8 data, none, 1 stopbit
8n2
8 data, none, 2 stopbit
bAud Baud rate
OFF; 0,3 ... 38,4 kBaud (ex works: 9,6)
The baud rate denotes the transmission rate at which one bit
is transmitted.
See interface-description: SST1300E
Download: www.elotech.de
EL.xx Control number
end of configuration level