4
Explosion Safety Parameters
38
IIB
IIA
Co
24
F
50
F
Lo
1uH
1uH
5/
ELCORplus version only
KP 100 061 - SCR interface:
(SLOT 0 TERMINALS: A, B)
6
/
Uo = 8.0V
Io = 20mA
Po = 160mW
IIB
IIA
Co
14uF
100uF
Lo
4/
8uH
10uH
4/
Inductive concentration, max. 30m cable can be connected.
6/
The module has an impact on the basic type of protection - see the instructions.
KP 100 062 - NAMUR interface:
(SLOT 0 TERMINALS: NAMUR+, NAMUR-)
Uo = 10.0V
Io = 11mA
Po = 27mW
IIB
IIA
Co
20uF
100uF
Lo
1mH
1mH
Ui = 5,5 V
Ii = 1 mA
Pi = 1 mW
Ci = 0, Li = 0
KP 100 110 - RS485 interface:
(SLOT 1,2 TERMINALS: D+, D-, GND, U+)
7/
Ui = 10V
Ii = 0.15A
Pi = 0.33W
Ci = 4uF
Li = 0
7/
ELCOR includes the interface as a standard; not SLOT 1,2 TERMINALS.
KP 100 110 - RS232 interface:
(SLOT 1,2 TERMINALS: GND, CTS, RXD, TXD)
7/
Ui = 20V
Ii = 0.15A
Pi = 0.46W
Summary of Contents for DATCOM
Page 38: ...3 Technical Parameters 36 ...
Page 50: ...5 Installation and Commissioning 48 Fig 7 Examples of data plates ...
Page 83: ...5 Installation and Commissioning 81 Fig 37 Communication via RS232 RS485 using B RS module ...
Page 115: ...7 Technical Description of the Device 113 Fig 57 Functional diagram of ELCOR ...
Page 116: ...7 Technical Description of the Device 114 Fig 58 Functional diagram of ELCORplus ...
Page 122: ...7 Technical Description of the Device 120 Fig 61 Modem replacement ...
Page 159: ...10 Communication with the Device 157 packet ...
Page 174: ...12 Accessories 172 Fig 78 ELCORplus example of use of external modules ...
Page 213: ...Appendix 3 Compass Data Export 211 Preview of generated document ...
Page 215: ...Appendix 3 Compass Data Export 213 3 Export to XLS 4 Export to TXT DOC ...
Page 216: ...Appendix 3 Compass Data Export 214 ...
Page 217: ...Appendix 3 Compass Data Export 215 5 Export of graph ...