19
Turbo cooling cycle
Functional description
•
Temperature display shows the temperature of the chamber as default
•
Set point temperature could be modified within the range given by the parameters
SnLP
(-20°C) and
SnHP
(+3°). The Set point is regulated by the factory to the value
given by the parameter
SnLP
•
During the execution of the cycle the chamber’s temperature could be modified
•
Defrost process
is automatically activated after a period given by the value of
the
parameter
Sdin
(
2 hours
).
It means that Turbo cooling cycle is active for a period (
2 hours
) and after that the
defrost cycle starts to work properly. Then the working cycle returns to be active
again.
•
Turbo cooling cycle is independent from the guideline selected (NF or UK)