07/2009 - Art. Nr. 4200 1023 3700A
35
Start-up
Adjustment mode
Menu “PARAMETER”
Programming of supplementary functions
- This parameter enables the air flap stop to be set. This parameter (in degrees) may
be required with postventilation.
Standard setting
00.0°
- With this function, error messages which have accumulated in the error log may be
cleared (display indication: “EMPTY”). The next new error is written as no. 0 in the
error log.
- This function is used to activate or deactivate the "AIR PRESSURE SWITCH"
function Y: yes, N: no.
- "CONTROLLER ADDRESS" (factory setting at 10H).
Other addresses are possible: F7H, F0H, 77H, 70H, 37H, 30H, 17H.
- After confirming with “NEXT” in the “CONTROLLER ADDRESS” menu, the newly
set parameters are saved in the safety unit. The safety unit then switches back to
“THERMOSTATIC CUT-OFF”.
OR “THERMOSTATIC CUT-OFF”
UNIT DEPROGRAMMED
BURNER ACCESS
WRITE PARAMETERS
NEXT PREVIOUS
10H
CONTROLLER ADDRESS
NEXT PREVIOUS
Y
AIR PRESSURE SWITCH (FUEL OIL)
NEXT PREVIOUS
CLEAR FAULT MEMORY
NEXT PREVIOUS
00.0°
AIR FLAP SHUTDOWN POSITION
en