07/2009 - Art. Nr. 4200 1023 3700A
31
Start-up
Burner setting data
The above setting data are
basic adjustments
. The factory setting data are framed in bold. Under normal circumstances, the
setting will enable the burner to operate. In any event, carefully check the setting values. Corrections may be necessary
depending on the characteristics of your installation.
en
Mini
kW
Medi.
kW
Maxi
kW
Mini
kg/h
Medi.
kg/h
Maxi
kg/h
Mini
bar
Medi.
bar
Maxi
bar
Flap
positi.
ignition
P0 (°)
Flap
positi.
mini
P1 (°)
Valve
positi.
Medi.
P2 (°)
Flap
positi.
medi.
P3 (°)
Valve
positi.
maxi
P4 (°)
Flap
positi.
maxi
P9 (°)
166
230
310
3,75 +
2,00
14
20
26
11
11
18
15
14,5
16
22
28
40
45
225
350
450
5,00 +
2,50
19
30
36
12
12
20
20
22
25
30
40
50
55
166
320
500
3,75 +
3,75
14
27
38
11
11
22
30
14,5
16
22
35
45
60
200
410
540
4,50 +
4,50
18
36
47
11
11
22
40
19
23
30
40
50
60
Dimen-
sion
Y
mm
Air flap opening
Fuel oil flow
Pump pressure
Burner power
Model
VL
04.540
DP
Nozzles
45°B
Gph